Decision attackability and minimum trusted instrumentation for secure export curtailment in a real transformer-limited distribution feeder
The increasing digitalization of distribution feeders has amplified the operational role of field measurements in real-time curtailment and security-aware control. At the same time, it has expanded the cyber-physical attack surface, especially when export-limitation decisions are driven by measurement streams rather than fully trusted internal states. This paper studies that problem in a real feeder monitored through a heterogeneous multi-stage measurement fabric with six monitored nodes and both aggregate- and line-level active-power channels. Rather than focusing only on signal-layer anomaly detection, the paper formulates and evaluates decision attackability, namely, the ability of plausible measurement corruption to distort curtailment decisions and drive the feeder away from secure operation. A data-grounded workflow is developed from real operating data. From 8928 trusted 15-minute operating points, a stress-based procedure constructs 400 decision-critical operating states, all of which are transformer-limited and fully recoverable under the trusted benchmark curtailment logic. On top of this critical-state atlas, a library of 4308 plausible attacks is generated, covering aggregate export under-reporting, clipping, replay, and multistage line-consistency manipulation. From this library, one state-level representative realization is extracted for each of the 400 critical states, yielding a 400-case decision-evaluated set for cyber-operational assessment under the benchmark curtailment policy. Exact decision-level evaluation shows that the most dangerous attacks are concentrated in aggregate decision-facing channels: AGG_PAIR yields 100% hidden insecurity, AGG_SINGLE 97.35%, and CLIP_SINGLE 94.00%, whereas pure line-redistribution attacks remain benign under the studied policy. An exact trusted-instrumentation analysis then shows that trusting only two aggregate channels, {G1@MBT5, G1@MBT6}, is sufficient to eliminate all dangerous decision distortions over the modeled critical-state atlas. This result remains unchanged under equal-cost, group-weighted, and deployment-weighted hardening-burden scenarios. The results provide a rigorous and operationally interpretable path from cyber-deception analysis to sparse, budget-aware hardening design for real distribution feeders.
Authors
- M. Cresta
- Marco Maccioni (ORCID: https://orcid.org/0000-0003-1317-7158)
- A. Geri (ORCID: https://orcid.org/0000-0002-3416-1756)
- Tommaso Bragatto (ORCID: https://orcid.org/0000-0003-3964-4244)
- Francesca Santori (ORCID: https://orcid.org/0000-0001-6726-0497)
- Mostafa Jabari (ORCID: https://orcid.org/0000-0003-2169-9802)
Institutions
- ASM Terni (Italy) (IT)
- Sapienza University of Rome (IT)
Publication Details
- Journal
- Energy Reports
- Published
- 2026-11-27
- DOI
- https://doi.org/10.1016/j.egyr.2026.109914
- Primary Topic
- Smart Grid Security and Resilience
- Type
- article
- Field-Weighted Citation Impact
- 0.00