Year-Resolved Quasi-Static Time-Series Assessment of Photovoltaic Hosting Capacity in a 59-Bus 22 kV Egyptian Distribution Network Model
A year-resolved quasi-static time-series (QSTS) assessment of the 59-bus, 22 kV Cairo distribution network model of [11] (peak load 50.34 MW) gives an overvoltage-limited photovoltaic (PV) hosting capacity (HC) of 165% of peak load (HC95 over 200 random placements, 1.02 p.u. substation setpoint, 95% bootstrap CI 150-189%). Each scenario uses 8760 hourly AC load flows with PVGIS-SARAH3 irradiance and a national-scale load shape built from Ember monthly demand and the EEHC peak-day curve; no feeder measurements were available. A snapshot at the year's lowest daytime load with peak PV output reproduces the level (160%), so a well-chosen snapshot is adequate on this network, while an arbitrary 25%-load snapshot (115%) is far too conservative and a 24 h mean day (215%) overestimates the HC. Overvoltage occurs on average in about 4 h per year, at 11:00-12:00 local time in spring (mostly April), and the full-year HC95 stays within 165-170% across all 19 simulated years (2005-2023). Sensitivities to tilt, load level, time alignment and substation setpoint are reported; thermal limits, whose ratings are not published, are examined only under assumed values. To the author's knowledge, this is the first year-resolved AC QSTS HC study of an Egyptian MV network model found in the literature searched. The results are conditional on the stated assumptions.
Authors
- Karim Abouelenein (ORCID: https://orcid.org/0009-0006-4639-8204)
Publication Details
- Journal
- Research Square
- Published
- 2026-11-27
- DOI
- https://doi.org/10.21203/rs.3.rs-11881914/v1
- Primary Topic
- Optimal Power Flow Distribution
- Type
- preprint