Structural performance and demountability of a reversible connector for panelised light timber-framed building systems

This study investigates the component-level mechanical response, damage mechanisms, and post-overload demountability after monotonic testing of the AusCon interlocking aluminium-to-timber connector developed for narrow Australian panelised light timber-framed members. Sixty screw-withdrawal tests were conducted in machine-graded pine (MGP12). Mean maximum withdrawal loads were 3.2 kN for side grain and 3.6 kN for face grain. A two-sample t-test did not detect a statistically significant difference between the two orientations under the tested conditions, while the ETA-based characteristic predictions remained conservative. Fifteen independent symmetric two-connector assemblies, comprising 30 physical connectors, were then tested under out-of-plane shear, tension, and vertical shear, with the results reported on a per-connector-equivalent basis. Mean peak loads were 9.8 kN, 11.0 kN, and 15.4 kN, respectively. At 5 mm beyond peak, the three configurations retained 94.2 ± 2.7%, 74.8 ± 14.1%, and 98.0 ± 0.8% of F max , respectively. The shear configurations exhibited stable early post-peak load transfer, whereas tension showed greater and more variable softening associated with timber splitting. Analytical predictions were below the measured mean peak loads in all configurations, although the predicted tension characteristic capacity slightly exceeded the corresponding measured characteristic estimate. All tested assemblies could be disassembled, but plastically deformed screws and local thread damage indicate that inspection and component replacement may be required following overload. Preliminary numerical screening identified an approximately 8 mm tapered cap as a candidate for future physical testing. A full-scale sectional prototype demonstrated unloaded assembly-disassembly cycles using standard tools. The study therefore establishes a bounded monotonic component-level baseline for demountability and repair-oriented development. Further work should include physical testing of the candidate cap, cyclic loading, whole-wall validation, and long-term durability assessment before broader structural or material applications are considered.

Authors

Institutions

Publication Details

Journal
Construction and Building Materials
Published
2026-11-27
DOI
https://doi.org/10.1016/j.conbuildmat.2026.149055
Primary Topic
Structural Load-Bearing Analysis
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
article

Structural performance and demountability of a reversible connector for panelised light timber-framed building systems

Lisa-Mareike Ottenhaus, Zidi Yan, Paul Adams, Josef Kowal
Construction and Building Materials
Structural Load-Bearing Analysis
article

Structural performance and demountability of a reversible connector for panelised light timber-framed building systems

Lisa-Mareike Ottenhaus, Zidi Yan, Paul Adams, Josef Kowal
article en

Abstract

This study investigates the component-level mechanical response, damage mechanisms, and post-overload demountability after monotonic testing of the AusCon interlocking aluminium-to-timber connector developed for narrow Australian panelised light timber-framed members. Sixty screw-withdrawal tests were conducted in machine-graded pine (MGP12). Mean maximum withdrawal loads were 3.2 kN for side grain and 3.6 kN for face grain. A two-sample t-test did not detect a statistically significant difference between the two orientations under the tested conditions, while the ETA-based characteristic predictions remained conservative. Fifteen independent symmetric two-connector assemblies, comprising 30 physical connectors, were then tested under out-of-plane shear, tension, and vertical shear, with the results reported on a per-connector-equivalent basis. Mean peak loads were 9.8 kN, 11.0 kN, and 15.4 kN, respectively. At 5 mm beyond peak, the three configurations retained 94.2 ± 2.7%, 74.8 ± 14.1%, and 98.0 ± 0.8% of F max , respectively. The shear configurations exhibited stable early post-peak load transfer, whereas tension showed greater and more variable softening associated with timber splitting. Analytical predictions were below the measured mean peak loads in all configurations, although the predicted tension characteristic capacity slightly exceeded the corresponding measured characteristic estimate. All tested assemblies could be disassembled, but plastically deformed screws and local thread damage indicate that inspection and component replacement may be required following overload. Preliminary numerical screening identified an approximately 8 mm tapered cap as a candidate for future physical testing. A full-scale sectional prototype demonstrated unloaded assembly-disassembly cycles using standard tools. The study therefore establishes a bounded monotonic component-level baseline for demountability and repair-oriented development. Further work should include physical testing of the candidate cap, cyclic loading, whole-wall validation, and long-term durability assessment before broader structural or material applications are considered.

Construction and Building MaterialsVol. 552
The University of Queensland (AU), University of the Sunshine Coast (AU)
Structural Load-Bearing Analysis
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Laika access coming soon