Analiza obciążenia stacji transformatorowej w sieci elektroenergetycznej z odnawialnymi źródłami energii o dużej mocy
This paper presents the results of load measurements in a 110/15 kV transformer substation under conditions of high penetration of renewable energy sources in the medium-voltage grid. Characteristic daily active power profiles recorded during different seasons (winter, spring, and summer) are discussed, with particular emphasis on the reverse power flow phenomenon, i.e., backfeeding from the 15 kV grid to the 110 kV grid. The impact of load variation on the transformer oil temperature is analyzed, the voltage level in the substation is presented, and the risk of insulation durability reduction under long-term overload conditions is assessed. The mitigation measures proposed for implementation, aimed at reducing the negative impact of distributed high-power sources on the thermal conditions of the transformer, are discussed.