Analiza obciążenia stacji transformatorowej w sieci elektroenergetycznej z odnawialnymi źródłami energii o dużej mocy

This paper presents the results of load measurements in a 110/15 kV transformer substation under conditions of high penetration of renewable energy sources in the medium-voltage grid. Characteristic daily active power profiles recorded during different seasons (winter, spring, and summer) are discussed, with particular emphasis on the reverse power flow phenomenon, i.e., backfeeding from the 15 kV grid to the 110 kV grid. The impact of load variation on the transformer oil temperature is analyzed, the voltage level in the substation is presented, and the risk of insulation durability reduction under long-term overload conditions is assessed. The mitigation measures proposed for implementation, aimed at reducing the negative impact of distributed high-power sources on the thermal conditions of the transformer, are discussed.

Authors

Publication Details

Journal
PRZEGLĄD ELEKTROTECHNICZNY
Published
2026-11-26
DOI
https://doi.org/10.15199/48.2026.11.8
Primary Topic
Power Transformer Diagnostics and Insulation
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
article

Analiza obciążenia stacji transformatorowej w sieci elektroenergetycznej z odnawialnymi źródłami energii o dużej mocy

Tadeusz TRUMIŃSKI
PRZEGLĄD ELEKTROTECHNICZNY
Power Transformer Diagnostics and Insulation
article

Analiza obciążenia stacji transformatorowej w sieci elektroenergetycznej z odnawialnymi źródłami energii o dużej mocy

Tadeusz TRUMIŃSKI
article en

Abstract

This paper presents the results of load measurements in a 110/15 kV transformer substation under conditions of high penetration of renewable energy sources in the medium-voltage grid. Characteristic daily active power profiles recorded during different seasons (winter, spring, and summer) are discussed, with particular emphasis on the reverse power flow phenomenon, i.e., backfeeding from the 15 kV grid to the 110 kV grid. The impact of load variation on the transformer oil temperature is analyzed, the voltage level in the substation is presented, and the risk of insulation durability reduction under long-term overload conditions is assessed. The mitigation measures proposed for implementation, aimed at reducing the negative impact of distributed high-power sources on the thermal conditions of the transformer, are discussed.

PRZEGLĄD ELEKTROTECHNICZNYVol. 1(11)
Power Transformer Diagnostics and Insulation
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Laika access coming soon