Monitoring of supply voltage quality in a laboratory environment and its metrological implications
This paper presents power quality monitoring results from a university measurement laboratory. The measured THD averaged 3.35% – exU40 ceeding the 1% reference measurement threshold threefold – and the 9th harmonic exceeded its individual EN 50160 limit. The results indicate that supply voltage, while formally compliant with EN 50160, does not meet the more stringent requirements applicable to reference and qualification measurements; additionally, subharmonic components, a DC offset, and transient events were identified as relevant disturbance factors.
Authors
- Stanisław GALLA (ORCID: https://orcid.org/0000-0002-8769-082X)
Publication Details
- Journal
- PRZEGLĄD ELEKTROTECHNICZNY
- Published
- 2026-11-26
- DOI
- https://doi.org/10.15199/48.2026.11.12
- Primary Topic
- Power Quality and Harmonics
- Type
- article
- Field-Weighted Citation Impact
- 0.00