Comparative DGA-Based Fault Diagnosis and Root-Cause Assessment of Transformer using Duval Triangle and Pentagon Graphical Method
Power transformers are essential components of modern electrical power systems, and insulation degradation is one of the major contributors to transformer failure. This study presents a comparative root-cause assessment with DGA-based fault diagnosis, and insulation condition evaluation of real power transformers using the Duval Triangle and Duval Pentagon techniques. Dissolved Gas Analysis (DGA) has emerged as one of the most widely used techniques for diagnosing incipient faults in oil-filled transformers. Various DGA interpretation methods, including Rogers Ratio, IEC 60599, and Duval Triangle, have been extensively applied for fault identification. However, ratio- based techniques often suffer from diagnostic ambiguity due to overlapping fault boundaries. This paper presents a fault-based root cause of a failed power transformer using DGA diagnostic techniques. The study is based on real DGA data obtained from transformer oil sample collected after a transformer failure that occurred during the hot-climates at the high temperature, analyze internal fault mechanisms, various incipient fault classification were evaluated. Oil samples were investigated using various diagnostic techniques such as DRM, RRM and IEC 60599 standard, and the obtained results were compared with those derived from the Duval Triangle Method. The analysis revealed the presence of both electrical and thermal fault signatures in the oil samples, indicating severe deterioration of the internal insulation system.The results confirm the effectiveness of DGA for post-failure transformer diagnostics. DTM for accurate fault identification, condition assessment, and maintenance planning in power transformers. Hence, focus on advanced graphical methods for improving the effectiveness and efficiency of fault identification
Authors
- Chilaka Ranga (ORCID: https://orcid.org/0000-0001-6470-550X)
- Varsha Thakur
Institutions
- National Institute of Technology Raipur (IN)
Publication Details
- Journal
- Research Square
- Published
- 2026-11-26
- DOI
- https://doi.org/10.21203/rs.3.rs-10915328/v1
- Primary Topic
- Power Transformer Diagnostics and Insulation
- Type
- preprint