Influence of membrane design on pressure measurement in medium-voltage vacuum interrupters
Membrane pressure transducers are finding increasingly widespread application in real-time pressure monitoring and measurement systems dedicated to medium-voltage (MV) vacuum switching devices. This paper constitutes the substantive foundation for the design of a membrane-based diagnostic system for vacuum switching apparatus, intended to operate across a broad pressure range – from 10–4 Pa to 10⁵ Pa, encompassing both deep vacuum conditions and atmospheric pressure. The conducted simulation analysis demonstrated that the optimal elastic element for the diagnostic applications in question is a smooth, axisymmetric steel membrane with a thickness of 5·10–5 m, an outer diameter of 2,54·10–2 m, and an active working surface area of 5,067·10–4 m².
Authors
- Damian Kostyła (ORCID: https://orcid.org/0000-0002-9012-0158)
Publication Details
- Journal
- PRZEGLĄD ELEKTROTECHNICZNY
- Published
- 2026-11-26
- DOI
- https://doi.org/10.15199/48.2026.11.10
- Primary Topic
- Sensor Technology and Measurement Systems
- Type
- article
- Field-Weighted Citation Impact
- 0.00