Grey-Box Experimental Identification of Reduced-Order Models for Grid-Forming Converters
This paper proposes a grey-box system identification for identifying and validating reduced-order models (ROMs) of grid-forming (GFM) converters. Three reduced-order modeling techniques are compared within a common identification procedure: singular perturbation with frequency cutoff and participation factors (SP-PF), singular perturbation with energy residuals (SP-Energy), and balanced truncation (BT). Testing is on experimental data with real-life components. Results show that BT achieves the highest time-domain fit, followed by SP-Energy and SP-PF; SP-Energy better preserves key properties of the identified full-order model; BT places the dominant mode closest to the stability boundary and exhibits the highest sensitivity to parameter variations; SP-Energy outperforms SP-PF in both fit quality and consistency of modal preservation. Findings suggest that the model with the best time-domain fit does not always provide the most reliable representation of the modal properties for small-signal stability, with SP-Energy offering the best compromise between accuracy, physical interpretability, and modal preservation for the considered case study.
Authors
- Fabrizio Sossan (ORCID: https://orcid.org/0000-0002-7990-1471)
- Stephan Kenzelmann
- M. Saviozzi (ORCID: https://orcid.org/0000-0002-2290-4364)
- F. Silvestro (ORCID: https://orcid.org/0000-0002-2228-9832)
- Marcelo Cárdenas
Publication Details
- Journal
- arXiv
- Published
- 2026-11-25
- DOI
- https://doi.org/10.48550/arxiv.2611.34566
- Primary Topic
- Microgrid Control and Optimization
- Type
- preprint