Modelowanie i sterowanie układem przygotowania CWU zasilanym ciepłem odpadowym z klimatyzacji
This paper presents an analysis of the control of a domestic hot water (DHW) system powered by waste heat from air conditioning. Based on experimental studies, a mathematical model implemented in MATLAB/Simulink was developed and verified, achieving a temperature mapping error of −0.09°C to 0.20°C. Simulation studies confirmed the effectiveness of the proposed control strategy and demonstrated a temperature drop from 47.5°C to approximately 23.4°C during prolonged water consumption, confirming the validity of the additional heat source.
Authors
- Piotr Łyszczarz
Publication Details
- Journal
- PRZEGLĄD ELEKTROTECHNICZNY
- Published
- 2026-11-26
- DOI
- https://doi.org/10.15199/48.2026.11.5
- Primary Topic
- Building Energy and Comfort Optimization
- Type
- article
- Field-Weighted Citation Impact
- 0.00