CFD-guided design and optimization of an off-grid solar-powered refrigerator for fruit and vegetable storage in rural Sub-Saharan Africa

METHODS: A 50 L cabinet for 10 kg of mixed produce was designed for stand-alone rural operation from a 200 Wp photovoltaic (PV) module, an MPPT controller and a 0.8 kWh LiFePO4 battery. The hardware uses an R134a DC vapor-compression circuit, 40 mm polyurethane insulation, a 1.5 mm galvanized outer shell, a 1.0 mm aluminium liner, a rear microchannel evaporator, a perforated supply plenum, an electronically commutated fan and 1 kg of 5 °C phase-change material (PCM). Thermal performance was obtained from a fully specified three-dimensional ANSYS Fluent model that solves the transient Reynolds-averaged Navier-Stokes equations with Boussinesq buoyancy and the SST k-ω closure, Darcy-Forchheimer resistance in the produce stacks, conjugate energy equations for air, walls and produce, and an enthalpy-porosity PCM formulation, loosely coupled to an R134a compressor map and a PV/battery balance. Five discrete design cases (C0-C4) were ranked by a constrained multi-objective criterion on pull-down time, air-temperature spread ΔT, daily electrical energy E_d, cycle COP, useful-zone velocity and passive holdover, subject to explicit bounds on setpoint, energy, cost, fan speed, PV size and local manufacturability. DATA: Relative to the unmanaged baseline cabinet, the selected configuration C4 reduced the cyclic air-temperature spread from 6.4 °C to 2.0 °C, shortened 10 kg pull-down from 3.6 h to 2.5 h, and lowered predicted daily energy at 35 °C from 0.68 to 0.51 kWh day-1 (COP = 1.62). At 43 °C ambient the same cabinet remained at 0.74 kWh day-1. The PCM pack provided 4.0 h of passive holdover after a power cut. A conventional grid-powered 50 L compact refrigerator serving the same 10 kg load with twelve 30 s door openings at 35 °C is estimated, from published compact-appliance ratings derated to tropical duty, to consume 0.90-1.10 kWh day-1. C4 therefore uses 43-54% less electricity than that conventional baseline, or 143-215 kWh year-1, without drawing any grid energy. Refrigerator hardware is costed at approximately USD 294 and the complete off-grid kit at USD 569. Mesh M3 (0.98 × 106 cells) has a fine-grid GCI of 0.8% on mean air temperature; the domain heat-balance error is 0.7%. CONCLUSION: The first-order design lever is cabinet airflow management, not compressor oversizing: the plenum accounts for most of the uniformity and pull-down gain, while the PCM is a resilience lever that trades 0.2 h of pull-down for 4.0 h of holdover. The resulting appliance is locally fabricable, but R134a charging and recovery must be performed only by a trained refrigeration technician. Commodity-specific setpoints and prototype validation against the defined outputs remain prerequisites for field deployment.

Authors

Institutions

Publication Details

Journal
PLoS ONE
Published
2026-11-25
DOI
https://doi.org/10.1371/journal.pone.0363334
Primary Topic
Refrigeration and Air Conditioning Technologies
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
article

CFD-guided design and optimization of an off-grid solar-powered refrigerator for fruit and vegetable storage in rural Sub-Saharan Africa

Vicent Marwa
PLoS ONE
Refrigeration and Air Conditioning Technologies
article

CFD-guided design and optimization of an off-grid solar-powered refrigerator for fruit and vegetable storage in rural Sub-Saharan Africa

Vicent Marwa
article en

Abstract

METHODS: A 50 L cabinet for 10 kg of mixed produce was designed for stand-alone rural operation from a 200 Wp photovoltaic (PV) module, an MPPT controller and a 0.8 kWh LiFePO4 battery. The hardware uses an R134a DC vapor-compression circuit, 40 mm polyurethane insulation, a 1.5 mm galvanized outer shell, a 1.0 mm aluminium liner, a rear microchannel evaporator, a perforated supply plenum, an electronically commutated fan and 1 kg of 5 °C phase-change material (PCM). Thermal performance was obtained from a fully specified three-dimensional ANSYS Fluent model that solves the transient Reynolds-averaged Navier-Stokes equations with Boussinesq buoyancy and the SST k-ω closure, Darcy-Forchheimer resistance in the produce stacks, conjugate energy equations for air, walls and produce, and an enthalpy-porosity PCM formulation, loosely coupled to an R134a compressor map and a PV/battery balance. Five discrete design cases (C0-C4) were ranked by a constrained multi-objective criterion on pull-down time, air-temperature spread ΔT, daily electrical energy E_d, cycle COP, useful-zone velocity and passive holdover, subject to explicit bounds on setpoint, energy, cost, fan speed, PV size and local manufacturability. DATA: Relative to the unmanaged baseline cabinet, the selected configuration C4 reduced the cyclic air-temperature spread from 6.4 °C to 2.0 °C, shortened 10 kg pull-down from 3.6 h to 2.5 h, and lowered predicted daily energy at 35 °C from 0.68 to 0.51 kWh day-1 (COP = 1.62). At 43 °C ambient the same cabinet remained at 0.74 kWh day-1. The PCM pack provided 4.0 h of passive holdover after a power cut. A conventional grid-powered 50 L compact refrigerator serving the same 10 kg load with twelve 30 s door openings at 35 °C is estimated, from published compact-appliance ratings derated to tropical duty, to consume 0.90-1.10 kWh day-1. C4 therefore uses 43-54% less electricity than that conventional baseline, or 143-215 kWh year-1, without drawing any grid energy. Refrigerator hardware is costed at approximately USD 294 and the complete off-grid kit at USD 569. Mesh M3 (0.98 × 106 cells) has a fine-grid GCI of 0.8% on mean air temperature; the domain heat-balance error is 0.7%. CONCLUSION: The first-order design lever is cabinet airflow management, not compressor oversizing: the plenum accounts for most of the uniformity and pull-down gain, while the PCM is a resilience lever that trades 0.2 h of pull-down for 4.0 h of holdover. The resulting appliance is locally fabricable, but R134a charging and recovery must be performed only by a trained refrigeration technician. Commodity-specific setpoints and prototype validation against the defined outputs remain prerequisites for field deployment.

PLoS ONEVol. 21(11)
Mbeya University of Science and Technology (TZ)
Affordable and clean energy, Climate action, Industry, innovation and infrastructure
Refrigeration and Air Conditioning Technologies
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Laika access coming soon