Quantifying uncertainties in cooling load predictions by using dropout as a Bayesian approximation

Day-ahead load forecasts support chiller scheduling and ice-storage control, but deterministic predictions do not quantify reliability. This study develops an artificial neural network with Monte Carlo dropout (ANN + MC-Dropout) to estimate epistemic and aleatoric uncertainty. The framework was initially evaluated using actual day-ahead weather forecasts collected and archived from Dark Sky at issuance. A validation-block sensitivity analysis examined model capacity and dropout rate. Separately, a controlled benchmark across four buildings in Taipei compared ANN + MC-Dropout with deep ensemble, quantile regression, and GRU + MC-Dropout models for cooling and electricity loads. This benchmark used observed weather for the target day (perfect-prognosis conditions) to isolate model performance. All methods shared a nine-point hidden-width/learning-rate search grid, with method-specific settings fixed, and were evaluated over three independent runs using probabilistic scoring rules, validation-based recalibration, and Diebold–Mariano tests. Under perfect-prognosis conditions, ANN + MC-Dropout achieved R² = 0.872–0.977 and PICP@95% = 0.917–0.958 without post-hoc recalibration. Accuracy differences were modest, and no method consistently dominated. After recalibration, weighted interval scores among the three dense-network methods differed by at most 4%. Controlled experiments showed that epistemic uncertainty decreased with training-set size, while aleatoric variance captured 61–67% of injected label-noise variance, indicating an approximate uncertainty decomposition. Overall, ANN + MC-Dropout offers a practical approach to probabilistic building-load forecasting.

Authors

Institutions

Publication Details

Journal
Energy Reports
Published
2026-11-25
DOI
https://doi.org/10.1016/j.egyr.2026.109953
Primary Topic
Building Energy and Comfort Optimization
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
article

Quantifying uncertainties in cooling load predictions by using dropout as a Bayesian approximation

Ying-Chieh Chan, Yih-Shiuan CHANG, Kuan-Chun Shih
1 links
Energy Reports
Building Energy and Comfort Optimization
article

Quantifying uncertainties in cooling load predictions by using dropout as a Bayesian approximation

Ying-Chieh Chan, Yih-Shiuan CHANG, Kuan-Chun Shih
article en

Abstract

Day-ahead load forecasts support chiller scheduling and ice-storage control, but deterministic predictions do not quantify reliability. This study develops an artificial neural network with Monte Carlo dropout (ANN + MC-Dropout) to estimate epistemic and aleatoric uncertainty. The framework was initially evaluated using actual day-ahead weather forecasts collected and archived from Dark Sky at issuance. A validation-block sensitivity analysis examined model capacity and dropout rate. Separately, a controlled benchmark across four buildings in Taipei compared ANN + MC-Dropout with deep ensemble, quantile regression, and GRU + MC-Dropout models for cooling and electricity loads. This benchmark used observed weather for the target day (perfect-prognosis conditions) to isolate model performance. All methods shared a nine-point hidden-width/learning-rate search grid, with method-specific settings fixed, and were evaluated over three independent runs using probabilistic scoring rules, validation-based recalibration, and Diebold–Mariano tests. Under perfect-prognosis conditions, ANN + MC-Dropout achieved R² = 0.872–0.977 and PICP@95% = 0.917–0.958 without post-hoc recalibration. Accuracy differences were modest, and no method consistently dominated. After recalibration, weighted interval scores among the three dense-network methods differed by at most 4%. Controlled experiments showed that epistemic uncertainty decreased with training-set size, while aleatoric variance captured 61–67% of injected label-noise variance, indicating an approximate uncertainty decomposition. Overall, ANN + MC-Dropout offers a practical approach to probabilistic building-load forecasting.

Energy ReportsVol. 16
National Taiwan University (TW), China Medical University (TW), China Medical University (CN)
Affordable and clean energy, Climate action
Building Energy and Comfort Optimization
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Laika access coming soon