Harmonic Resonance in Detuned Low-Voltage Power-Factor Correction Capacitor Banks: Failure Analysis at a Transformer Manufacturing Plant and Remedial Measures

This paper investigates three successive capacitor failures that occurred between December 2025 and May 2026 in two 440 V power-factor correction (PFC) cabinets of a transformer manufacturing plant in Bac Ninh Industrial Park, Vietnam. Each 100 kvar stage of the cabinets consists of two 50 kvar capacitors connected in series with a 7% detuning reactor. A seven-day power quality survey with Kyoritsu KEW 6315 and Hioki PQ3100 analysers was complemented by an on-site resonance sweep, in which the capacitance connected to one reactor was varied between 50 kvar and 110–120 kvar, so that the relative tuning order of the branch moved between 5.35 and 3.45. As the tuning approached the 5th order, the 5th-harmonic capacitor current rose to 150% (MSB1) and 230% (MSB2) of the fundamental component, and the corresponding harmonic voltage across the capacitors reached 27% and 42.9%, respectively. Stress indices evaluated according to IEEE Std 18-2012 confirm that the rms current, peak voltage and reactive power of the capacitors exceeded their continuous-operation limits, the rms current reaching 2.6 times the rated value. The root cause is traced to the 7% reactor (ℎ𝑟≈3.78), which is inappropriate for a harmonic spectrum containing appreciable 2nd- and 4th-order components, and a self-reinforcing failure mechanism is identified in which capacitance loss progressively drives the branch tuning towards the 5th order. Two remedies are compared, namely an adaptive passive filter with variable resonance frequency combined with reactive power compensation, and the replacement of the 7% reactors by 14% reactors; the former is recommended.

Authors

Publication Details

Journal
Zenodo (CERN European Organization for Nuclear Research)
Published
2026-11-25
DOI
https://doi.org/10.5281/zenodo.24525456
Primary Topic
Power Quality and Harmonics
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
article

Harmonic Resonance in Detuned Low-Voltage Power-Factor Correction Capacitor Banks: Failure Analysis at a Transformer Manufacturing Plant and Remedial Measures

Đinh Ngọc Quang, Jun Tan Joe
Zenodo (CERN European Organization for Nuclear Research)
Power Quality and Harmonics
article

Harmonic Resonance in Detuned Low-Voltage Power-Factor Correction Capacitor Banks: Failure Analysis at a Transformer Manufacturing Plant and Remedial Measures

Đinh Ngọc Quang, Jun Tan Joe
article en

Abstract

This paper investigates three successive capacitor failures that occurred between December 2025 and May 2026 in two 440 V power-factor correction (PFC) cabinets of a transformer manufacturing plant in Bac Ninh Industrial Park, Vietnam. Each 100 kvar stage of the cabinets consists of two 50 kvar capacitors connected in series with a 7% detuning reactor. A seven-day power quality survey with Kyoritsu KEW 6315 and Hioki PQ3100 analysers was complemented by an on-site resonance sweep, in which the capacitance connected to one reactor was varied between 50 kvar and 110–120 kvar, so that the relative tuning order of the branch moved between 5.35 and 3.45. As the tuning approached the 5th order, the 5th-harmonic capacitor current rose to 150% (MSB1) and 230% (MSB2) of the fundamental component, and the corresponding harmonic voltage across the capacitors reached 27% and 42.9%, respectively. Stress indices evaluated according to IEEE Std 18-2012 confirm that the rms current, peak voltage and reactive power of the capacitors exceeded their continuous-operation limits, the rms current reaching 2.6 times the rated value. The root cause is traced to the 7% reactor (ℎ𝑟≈3.78), which is inappropriate for a harmonic spectrum containing appreciable 2nd- and 4th-order components, and a self-reinforcing failure mechanism is identified in which capacitance loss progressively drives the branch tuning towards the 5th order. Two remedies are compared, namely an adaptive passive filter with variable resonance frequency combined with reactive power compensation, and the replacement of the 7% reactors by 14% reactors; the former is recommended.

Zenodo (CERN European Organization for Nuclear Research)
Power Quality and Harmonics
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Laika access coming soon