A transformer-configuration-aware incremental directional protection scheme for inverter-based resources

Inverter-based resources (IBRs) supply fault currents that differ fundamentally from those of synchronous generators, challenging conventional protective relays. While prior studies have focused on positive-sequence fault currents, the negative- and zero-sequence responses of IBRs under unsymmetrical faults, and their dependence on transformer winding connections and grounding, remain insufficiently understood. Using real-time electromagnetic transient simulations, we characterize the sequence currents during balanced and unbalanced faults under four transformer winding connections. The positive-sequence current remains below 1.1 p.u., the negative-sequence current stays below 0.07 p.u., and zero-sequence current appears only for ground faults with a grounded Y-connected transformer, leaving conventional protection with little to act on. Building on this analysis, we develop an incremental focused directional protection scheme that compares each voltage and current sample with its value one cycle earlier. Faults are detected from the change ratio of incremental quantities (K R) and the maximum absolute incremental angle (| Δ θ | max), and the trip is supervised by a directional condition on the fault-period voltage-current angle, without requiring line impedance data or sequence currents. Simulation results across diverse fault types, transformer connections, and system conditions show that both detection metrics exceeded their thresholds for all tested faults, while load and capacitor switching produced responses well below the thresholds. High-impedance faults up to 400 Ω were detected, and all tested reverse faults were correctly blocked. Compared with conventional phase overcurrent and zero-sequence protection, the proposed scheme provided broader fault coverage across the tested fault types and transformer connections.

Authors

Institutions

Publication Details

Journal
Frontiers in Energy Research
Published
2026-11-25
DOI
https://doi.org/10.3389/fenrg.2026.2021496
Primary Topic
Power Systems Fault Detection
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
article

A transformer-configuration-aware incremental directional protection scheme for inverter-based resources

Abu Shouaib Hasan, Rui Fan, Md Samsul Alam
Frontiers in Energy Research
Power Systems Fault Detection
article

A transformer-configuration-aware incremental directional protection scheme for inverter-based resources

Abu Shouaib Hasan, Rui Fan, Md Samsul Alam
article en

Abstract

Inverter-based resources (IBRs) supply fault currents that differ fundamentally from those of synchronous generators, challenging conventional protective relays. While prior studies have focused on positive-sequence fault currents, the negative- and zero-sequence responses of IBRs under unsymmetrical faults, and their dependence on transformer winding connections and grounding, remain insufficiently understood. Using real-time electromagnetic transient simulations, we characterize the sequence currents during balanced and unbalanced faults under four transformer winding connections. The positive-sequence current remains below 1.1 p.u., the negative-sequence current stays below 0.07 p.u., and zero-sequence current appears only for ground faults with a grounded Y-connected transformer, leaving conventional protection with little to act on. Building on this analysis, we develop an incremental focused directional protection scheme that compares each voltage and current sample with its value one cycle earlier. Faults are detected from the change ratio of incremental quantities (K R) and the maximum absolute incremental angle (| Δ θ | max), and the trip is supervised by a directional condition on the fault-period voltage-current angle, without requiring line impedance data or sequence currents. Simulation results across diverse fault types, transformer connections, and system conditions show that both detection metrics exceeded their thresholds for all tested faults, while load and capacitor switching produced responses well below the thresholds. High-impedance faults up to 400 Ω were detected, and all tested reverse faults were correctly blocked. Compared with conventional phase overcurrent and zero-sequence protection, the proposed scheme provided broader fault coverage across the tested fault types and transformer connections.

Frontiers in Energy ResearchVol. 14
University of Denver (US), GE Vernova (United States) (US)
Power Systems Fault Detection
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Laika access coming soon