Grid-forming SVG DC-side hybrid capacitor series topology and capacity design method
Introduction Grid-forming (GFM) static var generators (SVGs) require adequate DC-side energy storage to provide transient active-power support during grid-frequency disturbances. This study aims to reduce supercapacitor requirements while maintaining the transient support capability of GFM SVGs. Methods A series hybrid DC-side topology combining supercapacitors and electrolytic capacitors with a bidirectional partial-power DC/DC converter is proposed. An 800 V direct-connected all-supercapacitor system serves as the benchmark. An energy-equivalent synchronization method and a coordinated engineering sizing procedure are developed for realizable commercial-cell banks and the partial-power converter. Results Using identical 3.0 V/50 F cells, the benchmark and proposed systems require 297s1p and 75s1p supercapacitor banks, respectively. This represents a 74.75% reduction in supercapacitor cell count and the corresponding aggregate cell mass and geometrical volume relative to the specified benchmark. The selected DC/DC converter is rated at 2.114 kW, equivalent to 21.14% of the 10 kW SVG rating. Under the investigated consecutive disturbances with finite rates of change of frequency (RoCoF), the proposed system’s individual decline-stage peak support is approximately 1.52% lower than that of the benchmark. At the time of the benchmark system’s peak, the proposed system’s support is approximately 16.44% lower. The maximum normalized pointwise active-power difference reaches 30.23% during frequency recovery. The proposed system crosses the adopted 10% threshold 1 ms earlier; this is reported only as a diagnostic timing comparison. Discussion Under the investigated operating conditions, the proposed topology substantially reduces supercapacitor-cell requirements while using a converter rated at 21.14% of the SVG rating. It maintains comparable individual peak-support magnitudes and bidirectional energy-exchange characteristics, although the two systems have different peak timing and instantaneous active-power trajectories, particularly during frequency recovery.
Authors
- Pengliang Xu (ORCID: https://orcid.org/0009-0003-1595-9804)
- Chao Gong (ORCID: https://orcid.org/0000-0001-7319-1942)
- Yaohan Wang (ORCID: https://orcid.org/0000-0002-8652-1311)
- Haitao Liu
- Yan Li
Institutions
- State Grid Corporation of China (China) (CN)
Publication Details
- Journal
- Frontiers in Energy Research
- Published
- 2026-11-24
- DOI
- https://doi.org/10.3389/fenrg.2026.1890252
- Primary Topic
- Power Systems and Renewable Energy
- Type
- article
- Field-Weighted Citation Impact
- 0.00
Funders
- Electric Power Research Institute
- China Electric Power Research Institute
- Science and Technology Project of State Grid