Grid-forming SVG DC-side hybrid capacitor series topology and capacity design method

Introduction Grid-forming (GFM) static var generators (SVGs) require adequate DC-side energy storage to provide transient active-power support during grid-frequency disturbances. This study aims to reduce supercapacitor requirements while maintaining the transient support capability of GFM SVGs. Methods A series hybrid DC-side topology combining supercapacitors and electrolytic capacitors with a bidirectional partial-power DC/DC converter is proposed. An 800 V direct-connected all-supercapacitor system serves as the benchmark. An energy-equivalent synchronization method and a coordinated engineering sizing procedure are developed for realizable commercial-cell banks and the partial-power converter. Results Using identical 3.0 V/50 F cells, the benchmark and proposed systems require 297s1p and 75s1p supercapacitor banks, respectively. This represents a 74.75% reduction in supercapacitor cell count and the corresponding aggregate cell mass and geometrical volume relative to the specified benchmark. The selected DC/DC converter is rated at 2.114 kW, equivalent to 21.14% of the 10 kW SVG rating. Under the investigated consecutive disturbances with finite rates of change of frequency (RoCoF), the proposed system’s individual decline-stage peak support is approximately 1.52% lower than that of the benchmark. At the time of the benchmark system’s peak, the proposed system’s support is approximately 16.44% lower. The maximum normalized pointwise active-power difference reaches 30.23% during frequency recovery. The proposed system crosses the adopted 10% threshold 1 ms earlier; this is reported only as a diagnostic timing comparison. Discussion Under the investigated operating conditions, the proposed topology substantially reduces supercapacitor-cell requirements while using a converter rated at 21.14% of the SVG rating. It maintains comparable individual peak-support magnitudes and bidirectional energy-exchange characteristics, although the two systems have different peak timing and instantaneous active-power trajectories, particularly during frequency recovery.

Authors

Institutions

Publication Details

Journal
Frontiers in Energy Research
Published
2026-11-24
DOI
https://doi.org/10.3389/fenrg.2026.1890252
Primary Topic
Power Systems and Renewable Energy
Type
article
Field-Weighted Citation Impact
0.00

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
article

Grid-forming SVG DC-side hybrid capacitor series topology and capacity design method

Pengliang Xu, Chao Gong, Yaohan Wang, Haitao Liu et al.
4 links
Frontiers in Energy Research
Power Systems and Renewable Energy
article

Grid-forming SVG DC-side hybrid capacitor series topology and capacity design method

Pengliang Xu, Chao Gong, Yaohan Wang, Haitao Liu, Yan Li
article en

Abstract

Introduction Grid-forming (GFM) static var generators (SVGs) require adequate DC-side energy storage to provide transient active-power support during grid-frequency disturbances. This study aims to reduce supercapacitor requirements while maintaining the transient support capability of GFM SVGs. Methods A series hybrid DC-side topology combining supercapacitors and electrolytic capacitors with a bidirectional partial-power DC/DC converter is proposed. An 800 V direct-connected all-supercapacitor system serves as the benchmark. An energy-equivalent synchronization method and a coordinated engineering sizing procedure are developed for realizable commercial-cell banks and the partial-power converter. Results Using identical 3.0 V/50 F cells, the benchmark and proposed systems require 297s1p and 75s1p supercapacitor banks, respectively. This represents a 74.75% reduction in supercapacitor cell count and the corresponding aggregate cell mass and geometrical volume relative to the specified benchmark. The selected DC/DC converter is rated at 2.114 kW, equivalent to 21.14% of the 10 kW SVG rating. Under the investigated consecutive disturbances with finite rates of change of frequency (RoCoF), the proposed system’s individual decline-stage peak support is approximately 1.52% lower than that of the benchmark. At the time of the benchmark system’s peak, the proposed system’s support is approximately 16.44% lower. The maximum normalized pointwise active-power difference reaches 30.23% during frequency recovery. The proposed system crosses the adopted 10% threshold 1 ms earlier; this is reported only as a diagnostic timing comparison. Discussion Under the investigated operating conditions, the proposed topology substantially reduces supercapacitor-cell requirements while using a converter rated at 21.14% of the SVG rating. It maintains comparable individual peak-support magnitudes and bidirectional energy-exchange characteristics, although the two systems have different peak timing and instantaneous active-power trajectories, particularly during frequency recovery.

Frontiers in Energy ResearchVol. 14
State Grid Corporation of China (China) (CN)
Electric Power Research Institute, China Electric Power Research Institute, Science and Technology Project of State Grid
Affordable and clean energy, Industry, innovation and infrastructure
Power Systems and Renewable Energy
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Laika access coming soon