High-accuracy measurement of external characteristics of new-type power-electronic loads based on a four-virtual-phasor DFT algorithm

External-characteristic models of new-type power-electronic loads—data-centre rectifier supplies, battery-storage converters and fast chargers—are a prerequisite for the stability analysis of converter-dominated power systems, and both the model-driven and the data-driven modelling routes ultimately rest on the accuracy of the measured voltage and current phasors. This paper addresses the modelling bottleneck from the measurement-algorithm side: a four-virtual-phasor DFT (4VP-DFT) estimator, which analytically cancels the constant and first-order terms of the spectral-leakage-induced dynamic error and shapes an equivalent combined window that suppresses off-bin interferers, is generalized from synchrophasor measurement to the measurement of both faces of the external characteristic of a 2 MVA grid-feeding rectifier-type load. The design properties are established as three propositions with closed-form proofs, and the estimator is benchmarked against plain DFT, virtual-αβ, offset-π/3, interpolated-DFT (ipDFT) and second-order Taylor–Fourier baselines under an extended condition set (frequency offsets to ± 10 Hz, harmonic distortion up to 10% THD with 50 dB noise, out-of-band and interharmonic interference, amplitude–phase modulation and magnitude–phase steps) with Monte C arlo statistics over 200 randomized realizations. At a − 5 Hz offset the maximum phase error is 0.0095°, 37% below the best virtual-phasor baseline, and the 40 ms step response remains within the 70 ms limit; the estimator dominates every single-cycle-window baseline in the single-cycle latency class, whereas the multi-cycle baselines, although more accurate in stationary conditions, require two-to-three-cycle windows and degrade beyond ± 5 Hz. In the modelling loop, the static V–I characteristic is tracked with an RMSE of 4.69 kW (62% below the plain DFT), the wideband impedance is measured in 0.2 s windows with a mean magnitude error of 0.72% (plain DFT: 6.54%), and the impedance-based stability mar g ins reproduce the analytic ranking with a worst-case deviation of 33%. Joint identification of two drifted control parameters from the accurately measured impedance recovers the true values within 2.8% and 10.9% and reduces the model-to-data discrepancy from 55.0% to 8.73%, whereas the same procedure driven by plain-DFT measurements converges to a wrong model. The results establish phasor-measurement accuracy as the shared foundation of data-driven external-characteristic modelling, model validation and measurement-driven model correction for power-electronic loads.

Authors

Institutions

Publication Details

Journal
Research Square
Published
2026-11-23
DOI
https://doi.org/10.21203/rs.3.rs-11484424/v1
Primary Topic
Advanced Electrical Measurement Techniques
Type
preprint
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
preprint

High-accuracy measurement of external characteristics of new-type power-electronic loads based on a four-virtual-phasor DFT algorithm

Feiyang Xu, Li Chen, Chi Xu, Yu Wang et al.
Research Square
Advanced Electrical Measurement Techniques
preprint

High-accuracy measurement of external characteristics of new-type power-electronic loads based on a four-virtual-phasor DFT algorithm

Feiyang Xu, Li Chen, Chi Xu, Yu Wang, Min Zhang, Muyong Zhen
preprint en

Abstract

External-characteristic models of new-type power-electronic loads—data-centre rectifier supplies, battery-storage converters and fast chargers—are a prerequisite for the stability analysis of converter-dominated power systems, and both the model-driven and the data-driven modelling routes ultimately rest on the accuracy of the measured voltage and current phasors. This paper addresses the modelling bottleneck from the measurement-algorithm side: a four-virtual-phasor DFT (4VP-DFT) estimator, which analytically cancels the constant and first-order terms of the spectral-leakage-induced dynamic error and shapes an equivalent combined window that suppresses off-bin interferers, is generalized from synchrophasor measurement to the measurement of both faces of the external characteristic of a 2 MVA grid-feeding rectifier-type load. The design properties are established as three propositions with closed-form proofs, and the estimator is benchmarked against plain DFT, virtual-αβ, offset-π/3, interpolated-DFT (ipDFT) and second-order Taylor–Fourier baselines under an extended condition set (frequency offsets to ± 10 Hz, harmonic distortion up to 10% THD with 50 dB noise, out-of-band and interharmonic interference, amplitude–phase modulation and magnitude–phase steps) with Monte C arlo statistics over 200 randomized realizations. At a − 5 Hz offset the maximum phase error is 0.0095°, 37% below the best virtual-phasor baseline, and the 40 ms step response remains within the 70 ms limit; the estimator dominates every single-cycle-window baseline in the single-cycle latency class, whereas the multi-cycle baselines, although more accurate in stationary conditions, require two-to-three-cycle windows and degrade beyond ± 5 Hz. In the modelling loop, the static V–I characteristic is tracked with an RMSE of 4.69 kW (62% below the plain DFT), the wideband impedance is measured in 0.2 s windows with a mean magnitude error of 0.72% (plain DFT: 6.54%), and the impedance-based stability mar g ins reproduce the analytic ranking with a worst-case deviation of 33%. Joint identification of two drifted control parameters from the accurately measured impedance recovers the true values within 2.8% and 10.9% and reduces the model-to-data discrepancy from 55.0% to 8.73%, whereas the same procedure driven by plain-DFT measurements converges to a wrong model. The results establish phasor-measurement accuracy as the shared foundation of data-driven external-characteristic modelling, model validation and measurement-driven model correction for power-electronic loads.

Research Square
State Grid Corporation of China (China) (CN), Southeast University (CN)
Advanced Electrical Measurement Techniques
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Laika access coming soon