Power Quality Analysis of a Ceramic Manufacturing Unit Using Field Measurements

Power quality plays a significant role in the efficient operation and energy management of industrial facilities.Electrical issues such as voltage waveform distortion, harmonic currents, reactive power consumption, and low power factor can contribute to higher system loading and increased electrical losses.This study investigates the power quality performance of a continuously operating ceramic manufacturing unit located in Thangadh, Surendranagar, Gujarat, India, using actual field measurements.The selected small and medium-sized enterprise (SME) has a sanctioned electrical load of 100 kW and is supplied through the utility grid, with a diesel generator for backup and a 50 kW photovoltaic system.Electrical measurements were recorded using a three-phase power quality analyzer.The assessment included RMS voltage and current, system frequency, voltage and current total harmonic distortion (THD), active and reactive power, apparent power, distortion power, and overall power factor.The recorded phase voltages were 252.4 V, 250.1 V, and 250.0 V, with voltage THD values between 5.8% and 6.0%.In comparison, the current waveform showed considerably greater distortion, with current THD ranging from 15.4% to 17.5%.Under the measured operating condition, the facility consumed 36.78 kW of active power and 19.81 kVAr of reactive power.The corresponding distortion power and apparent power were 7.901 kVAr and 42.52 kVA, respectively, resulting in an overall power factor of 0.865.The relatively small variation among the three phase currents suggests that current imbalance was not a major concern during the measurement period.Instead, harmonic distortion and reactive power demand were identified as the more significant power quality issues.The study further examines the facility's existing 60 kVAr automatic power factor correction system, including the effect of a reported derated capacitor step.The findings indicate that combining on-site power quality measurements with conventional energy auditing provides a useful approach for identifying opportunities to improve power factor, reduce harmonic-related problems, and strengthen demand-side energy management in ceramic SMEs.

Authors

Institutions

Publication Details

Journal
IJIREEICE
Published
2026-11-23
DOI
https://doi.org/10.17148/ijireeice.2026.141116
Primary Topic
Power Quality and Harmonics
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
article

Power Quality Analysis of a Ceramic Manufacturing Unit Using Field Measurements

Dharmesh J. Pandya, Ankit B. Lehru
IJIREEICE
Power Quality and Harmonics
article

Power Quality Analysis of a Ceramic Manufacturing Unit Using Field Measurements

Dharmesh J. Pandya, Ankit B. Lehru
article en

Abstract

Power quality plays a significant role in the efficient operation and energy management of industrial facilities.Electrical issues such as voltage waveform distortion, harmonic currents, reactive power consumption, and low power factor can contribute to higher system loading and increased electrical losses.This study investigates the power quality performance of a continuously operating ceramic manufacturing unit located in Thangadh, Surendranagar, Gujarat, India, using actual field measurements.The selected small and medium-sized enterprise (SME) has a sanctioned electrical load of 100 kW and is supplied through the utility grid, with a diesel generator for backup and a 50 kW photovoltaic system.Electrical measurements were recorded using a three-phase power quality analyzer.The assessment included RMS voltage and current, system frequency, voltage and current total harmonic distortion (THD), active and reactive power, apparent power, distortion power, and overall power factor.The recorded phase voltages were 252.4 V, 250.1 V, and 250.0 V, with voltage THD values between 5.8% and 6.0%.In comparison, the current waveform showed considerably greater distortion, with current THD ranging from 15.4% to 17.5%.Under the measured operating condition, the facility consumed 36.78 kW of active power and 19.81 kVAr of reactive power.The corresponding distortion power and apparent power were 7.901 kVAr and 42.52 kVA, respectively, resulting in an overall power factor of 0.865.The relatively small variation among the three phase currents suggests that current imbalance was not a major concern during the measurement period.Instead, harmonic distortion and reactive power demand were identified as the more significant power quality issues.The study further examines the facility's existing 60 kVAr automatic power factor correction system, including the effect of a reported derated capacitor step.The findings indicate that combining on-site power quality measurements with conventional energy auditing provides a useful approach for identifying opportunities to improve power factor, reduce harmonic-related problems, and strengthen demand-side energy management in ceramic SMEs.

IJIREEICEVol. 14(11)
Atmiya University (IN)
Power Quality and Harmonics
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Laika access coming soon
Power Quality Analysis of a Ceramic Manufacturing Unit Using Field Measurements — Dharmesh J. Pandya, Ankit B. Lehru · IJIREEICE (2026) | TGRS Research Map | TGRS