Fast Transient-Voltage Risk Assessment of Renewable-Energy Clusters Using Spatial Operating States and Explicit Polynomial Surrogates
An explicit surrogate framework is developed for transient-voltage screening of renewable clusters near an HVDC sending terminal. Individual device powers and two pre-fault bus voltages form a 23-dimensional state. A 34-term polynomial predicts EMT-derived bus consequences for subsequent probability weighting. The original 912 EMT runs are supplemented by 144 runs across three renewable-injection levels, giving 340 admissible states. On 31 original frozen-model confirmation states, risk MAE is 3.079 × 10−6, with reductions of 75.6% and 32.3% relative to aggregate-power and device-power representations. On 47 accepted new states, severity MAE is 0.013301 and risk MAE is 3.0362 × 10−6 under illustrative one-hour event probabilities. Three equal-total-power redistribution pairs demonstrate location-dependent risk changes. Random forests and an artificial neural network improve original-cohort mean accuracy, while the polynomial retains a compact algebraic implementation. Measurement-noise tests reveal sensitivity to initial-voltage errors. Results support conditional screening within the tested network and control domain; field effectiveness and whole-system penetration transfer remain unvalidated.
Authors
- Qinglei Zhang
- Lei Luo (ORCID: https://orcid.org/0000-0002-2312-8715)
- Haibo Li (ORCID: https://orcid.org/0000-0002-7192-7458)
- Xiaoping Wang (ORCID: https://orcid.org/0000-0002-0105-4401)
- Dehai Zhang
- Yujing Song
Institutions
- State Grid Corporation of China (China) (CN)
- Tsinghua Sichuan Energy Internet Research Institute (CN)
- Tsinghua University (CN)
Publication Details
- Journal
- Processes
- Published
- 2026-11-23
- DOI
- https://doi.org/10.3390/pr14233765
- Primary Topic
- HVDC Systems and Fault Protection
- Type
- article
- Field-Weighted Citation Impact
- 0.00