How Much Curtailment Can a Data Center Safely Promise? Distributionally Robust Flexible-Interconnection Commitments for Cloud Campuses

Grid operators increasingly offer large loads faster interconnection in exchange for a promise to curtail during system stress, and system-level studies estimate that tens of gigawatts of new data-center load could be absorbed this way. A system-level headroom estimate, however, does not tell an individual cloud campus how many megawatts it can safely connect as non-firm load without breaching its own service-level agreements (SLAs). This paper formulates that question as a distributionally robust chance-constrained program. The campus chooses a non-firm commitment F; each curtailment event is covered at run time by four recourse levers—batch deferral, geographic shifting, battery discharge and GPU power capping—whose joint feasibility we characterize in closed form. Uncertainty in event duration, battery state of charge and heat-wave-correlated sister-site availability is captured by a type-1 Wasserstein ball around the empirical event history. We prove that the resulting worst-case breach probability is a fractional knapsack over each event’s log-distance to breach, so the robust constraint reduces to a lower-tail margin condition and the safe commitment F* is found by bisection. On a 100 MW campus calibrated to published curtailment statistics, sample-average commitments (21.0 MW) breach the SLA in 11.2% of events under a heat-wave stress test, whereas a robust commitment with radius θ = 0.01 (16.8 MW) keeps breaches at 3.8%, below the 5% target, and lowers the 95% conditional value-at-risk of annual recourse cost by 40%. An average-event rule of thumb over-promises by a factor of 1.7. A sensitivity map shows that batch-deferral slack longer than typical events is the single most valuable flexibility lever.

Authors

Publication Details

Journal
Indian Journal of Computer Science and Technology
Published
2026-11-23
DOI
https://doi.org/10.59256/indjcst.20260503105
Primary Topic
Electric Power System Optimization
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
article

How Much Curtailment Can a Data Center Safely Promise? Distributionally Robust Flexible-Interconnection Commitments for Cloud Campuses

P Tatsat
Indian Journal of Computer Science and Technology
Electric Power System Optimization
article

How Much Curtailment Can a Data Center Safely Promise? Distributionally Robust Flexible-Interconnection Commitments for Cloud Campuses

P Tatsat
article en

Abstract

Grid operators increasingly offer large loads faster interconnection in exchange for a promise to curtail during system stress, and system-level studies estimate that tens of gigawatts of new data-center load could be absorbed this way. A system-level headroom estimate, however, does not tell an individual cloud campus how many megawatts it can safely connect as non-firm load without breaching its own service-level agreements (SLAs). This paper formulates that question as a distributionally robust chance-constrained program. The campus chooses a non-firm commitment F; each curtailment event is covered at run time by four recourse levers—batch deferral, geographic shifting, battery discharge and GPU power capping—whose joint feasibility we characterize in closed form. Uncertainty in event duration, battery state of charge and heat-wave-correlated sister-site availability is captured by a type-1 Wasserstein ball around the empirical event history. We prove that the resulting worst-case breach probability is a fractional knapsack over each event’s log-distance to breach, so the robust constraint reduces to a lower-tail margin condition and the safe commitment F* is found by bisection. On a 100 MW campus calibrated to published curtailment statistics, sample-average commitments (21.0 MW) breach the SLA in 11.2% of events under a heat-wave stress test, whereas a robust commitment with radius θ = 0.01 (16.8 MW) keeps breaches at 3.8%, below the 5% target, and lowers the 95% conditional value-at-risk of annual recourse cost by 40%. An average-event rule of thumb over-promises by a factor of 1.7. A sensitivity map shows that batch-deferral slack longer than typical events is the single most valuable flexibility lever.

Indian Journal of Computer Science and Technology
Electric Power System Optimization
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Laika access coming soon