Design, Experimental Validation, and Numerical Coolant Comparison of a Compact Plate-Fin-and-Tube Rear Door Heat Exchanger with Al2O3 Nanofluid for Data Center Cooling
Rear door heat exchangers let an air-cooled rack reject heat to water without changes to the servers. This paper describes the design and rating of a hand-built plate-fin-and-tube door exchanger sized for 5 kW inside a 100 mm door depth. The 438-fin, two-row, two-pass core has a 50 mm longitudinal pitch, outside the stated range of the air-side correlation used to rate it. CFD of an air-side unit cell and of the water circuit was used to calibrate the air-side pressure drop model and the water-side coefficient, and a GT-SUITE rack model checked the design point and the response to a measured GPU load. The calibrated model predicts 5507 W at an air-side pressure drop of 15.4 Pa and agrees within 6.8% with a low-load bench test. Al2O3 nanofluid at 1 to 4% by volume gave no useful gain at equal pumping power.