Design, Experimental Validation, and Numerical Coolant Comparison of a Compact Plate-Fin-and-Tube Rear Door Heat Exchanger with Al2O3 Nanofluid for Data Center Cooling

Rear door heat exchangers let an air-cooled rack reject heat to water without changes to the servers. This paper describes the design and rating of a hand-built plate-fin-and-tube door exchanger sized for 5 kW inside a 100 mm door depth. The 438-fin, two-row, two-pass core has a 50 mm longitudinal pitch, outside the stated range of the air-side correlation used to rate it. CFD of an air-side unit cell and of the water circuit was used to calibrate the air-side pressure drop model and the water-side coefficient, and a GT-SUITE rack model checked the design point and the response to a measured GPU load. The calibrated model predicts 5507 W at an air-side pressure drop of 15.4 Pa and agrees within 6.8% with a low-load bench test. Al2O3 nanofluid at 1 to 4% by volume gave no useful gain at equal pumping power.

Authors

Institutions

Publication Details

Journal
Engineering Archive (engrXiv)
Published
2026-11-23
DOI
https://doi.org/10.31224/8886
Primary Topic
Heat Transfer and Optimization
Type
preprint
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
preprint

Design, Experimental Validation, and Numerical Coolant Comparison of a Compact Plate-Fin-and-Tube Rear Door Heat Exchanger with Al2O3 Nanofluid for Data Center Cooling

Anindya Guha, Md. Sabbir Hossain, Fatin Ishraque, Mohammad Sifat Hasan et al.
Engineering Archive (engrXiv)
Heat Transfer and Optimization
preprint

Design, Experimental Validation, and Numerical Coolant Comparison of a Compact Plate-Fin-and-Tube Rear Door Heat Exchanger with Al2O3 Nanofluid for Data Center Cooling

Anindya Guha, Md. Sabbir Hossain, Fatin Ishraque, Mohammad Sifat Hasan, Parag Mollick
preprint en

Abstract

Rear door heat exchangers let an air-cooled rack reject heat to water without changes to the servers. This paper describes the design and rating of a hand-built plate-fin-and-tube door exchanger sized for 5 kW inside a 100 mm door depth. The 438-fin, two-row, two-pass core has a 50 mm longitudinal pitch, outside the stated range of the air-side correlation used to rate it. CFD of an air-side unit cell and of the water circuit was used to calibrate the air-side pressure drop model and the water-side coefficient, and a GT-SUITE rack model checked the design point and the response to a measured GPU load. The calibrated model predicts 5507 W at an air-side pressure drop of 15.4 Pa and agrees within 6.8% with a low-load bench test. Al2O3 nanofluid at 1 to 4% by volume gave no useful gain at equal pumping power.

Engineering Archive (engrXiv)
Bangladesh University of Engineering and Technology (BD), Dhaka University of Engineering & Technology (BD)
Heat Transfer and Optimization
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Laika access coming soon
Design, Experimental Validation, and Numerical Coolant Comparison of a Compact Plate-Fin-and-Tube Rear Door Heat Exchanger with Al2O3 Nanofluid for Data Center Cooling — Anindya Guha, Md. Sabbir Hossain, et al. · Engineering Archive (engrXiv) (2026) | TGRS Research Map | TGRS