EXPERIMENTAL INVESTIGATION OF THE EFFECT OF DIFFERENT RECTIFIER TOPOLOGIES ON OUTPUT VOLTAGE AND TOTAL HARMONIC DISTORTION IN SYNCHRONOUS ALTERNATOR EXCITATION

In this study, the effects of supplying the field (excitation) winding of a synchronous alternator through single-phase half-wave, single-phase full-wave, three-phase half-wave (3-pulse), and three-phase full-wave (6-pulse) rectifier circuits on the no-load stator output voltage and total harmonic distortion were experimentally investigated. The test machine was a synchronous alternator with the following nameplate specifications: 220/380 V (Δ/Y), 2.9/1.7 A (Δ/Y), 1.1 kVA, power factor cos φ = 0.8, rated speed 3000 rpm, 2p = 2 poles, 50 Hz. The measured field winding resistance was R = 197.2 Ω and inductance L = 1743.3 mH, yielding a time constant τ = L/R ≈ 8.84 ms. Measurements were performed on the stator phase-to-neutral voltages using a True RMS power analyser with an accuracy class of ±1% ±1 digit and a harmonic measurement range up to the 40th order. Under excitation currents ranging from 100 mA to 300 mA, the stator phase voltage total harmonic distortion remained nearly constant at approximately 7.1%–8.4% across all rectifier topologies. This finding indicates that the high inductance of the field winding attenuates the supply voltage ripple, acting as a natural low-pass filter and producing a smooth direct current in the field circuit. The results suggest that, under no-load conditions and within the excitation current range studied, the dominant source of stator voltage harmonics is likely the internal design parameters of the alternator—such as stator–rotor geometry, slot pitch, and air-gap flux distribution—rather than the excitation supply topology. These findings are specific to the machine under investigation and the no-load operating conditions employed.

Authors

Institutions

Publication Details

Journal
International Journal of Energy and Smart Grid
Published
2026-11-22
DOI
https://doi.org/10.55088/ijesg.2059401
Primary Topic
Power Quality and Harmonics
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
article

EXPERIMENTAL INVESTIGATION OF THE EFFECT OF DIFFERENT RECTIFIER TOPOLOGIES ON OUTPUT VOLTAGE AND TOTAL HARMONIC DISTORTION IN SYNCHRONOUS ALTERNATOR EXCITATION

Ahmet AYCAN, Mesut Özdinç, Mehmet Ali Özçelik
International Journal of Energy and Smart Grid
Power Quality and Harmonics
article

EXPERIMENTAL INVESTIGATION OF THE EFFECT OF DIFFERENT RECTIFIER TOPOLOGIES ON OUTPUT VOLTAGE AND TOTAL HARMONIC DISTORTION IN SYNCHRONOUS ALTERNATOR EXCITATION

Ahmet AYCAN, Mesut Özdinç, Mehmet Ali Özçelik
article en

Abstract

In this study, the effects of supplying the field (excitation) winding of a synchronous alternator through single-phase half-wave, single-phase full-wave, three-phase half-wave (3-pulse), and three-phase full-wave (6-pulse) rectifier circuits on the no-load stator output voltage and total harmonic distortion were experimentally investigated. The test machine was a synchronous alternator with the following nameplate specifications: 220/380 V (Δ/Y), 2.9/1.7 A (Δ/Y), 1.1 kVA, power factor cos φ = 0.8, rated speed 3000 rpm, 2p = 2 poles, 50 Hz. The measured field winding resistance was R = 197.2 Ω and inductance L = 1743.3 mH, yielding a time constant τ = L/R ≈ 8.84 ms. Measurements were performed on the stator phase-to-neutral voltages using a True RMS power analyser with an accuracy class of ±1% ±1 digit and a harmonic measurement range up to the 40th order. Under excitation currents ranging from 100 mA to 300 mA, the stator phase voltage total harmonic distortion remained nearly constant at approximately 7.1%–8.4% across all rectifier topologies. This finding indicates that the high inductance of the field winding attenuates the supply voltage ripple, acting as a natural low-pass filter and producing a smooth direct current in the field circuit. The results suggest that, under no-load conditions and within the excitation current range studied, the dominant source of stator voltage harmonics is likely the internal design parameters of the alternator—such as stator–rotor geometry, slot pitch, and air-gap flux distribution—rather than the excitation supply topology. These findings are specific to the machine under investigation and the no-load operating conditions employed.

International Journal of Energy and Smart GridVol. 11
Gaziantep İslam Bilim ve Teknoloji Üniversitesi (TR), Gaziantep University (TR)
Power Quality and Harmonics
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Laika access coming soon