DO RELIGAMENTO CONVENCIONAL À DECISÃO INFORMADA: REVISÃO CRÍTICA DE TRÊS ESTUDOS SOBRE RELIGAMENTO ADAPTATIVO E SELF-HEALING EM SISTEMAS DE POTÊNCIA
Fixed dead-time reclosing does not check whether the fault persists; smart grids allow measurement-based decisions. This work critically reviews three papers, selected purposively and non-systematically, on adaptive reclosing in transmission and self-healing in distribution, and produces a comparison matrix, a table of extracted results and a list of gaps. In the test networks of one study, the MISOCP reference solution decided in under 1 s, and the faster reinforcement learning policy served 7.9% to 18.9% less energy. The distribution studies lack field validation, and the review reports no tests of its own; integrating decision-making with protection and communication remains open.
Authors
- Marcelo Henrique Fernandes
- Felipe Alves
- Sérgio Andrade
- João Batista Nascimento
- João Gabriel Gomes
Institutions
- Universidade Santa Cecília (BR)
Publication Details
- Journal
- Anais do Congresso Brasileiro de Iniciação Científica
- Published
- 2026-11-22
- DOI
- https://doi.org/10.66221/wsdbvc85
- Primary Topic
- Power Systems Fault Detection
- Type
- article
- Field-Weighted Citation Impact
- 0.00