Reliability improvement of distribution networks through optimal recloser placement considering photovoltaic resource allocation and sizing with protection coordination constraints

This study presents an integrated optimization framework for the optimal placement of reclosers and the simultaneous determination of the location and capacity of photovoltaic (PV) units in distribution networks. Unlike conventional approaches that treat the placement of protection devices and PV allocation as separate planning problems, the proposed method addresses both problems simultaneously and evaluates the impact of PV integration on protection performance and network reliability. Within this framework, recloser placement aims to improve reliability indices, including SAIFI, SAIDI, and ENS, while the locations of PV units and the maximum hosting capacity are determined subject to network voltage constraints. In addition, the coordination constraint between the recloser and cut-out fuse is incorporated into the objective function as a penalty term to ensure proper protection coordination and maintain the fuse-saving strategy. The optimization problem is solved using a search algorithm, and the proposed method is evaluated on the IEEE 33-bus test system. In Scenario 2, Bus 29 is identified as the optimal location for a PV unit with a capacity equivalent to 70% of the total network load, resulting in an improved voltage profile. In Scenario 3, with the recloser optimally placed on Line 1, the ENS, SAIFI, and SAIDI values are 36.82 (MWh/yr), 5.58 (int/cus/yr) and 9.12 (h/cus/yr), respectively. Furthermore, the short-circuit analysis of faults downstream of the cut-out fuses confirms that the recloser–fuse coordination constraint is satisfied both with and without PV integration. The results demonstrate that the proposed framework can simultaneously optimize recloser placement and PV allocation while maintaining proper protection coordination and the fuse-saving strategy. It also enables an increase in PV hosting capacity subject to voltage constraints and improves network reliability.

Authors

Institutions

Publication Details

Journal
Scientific Reports
Published
2026-11-20
DOI
https://doi.org/10.1038/s41598-026-81218-1
Primary Topic
Optimal Power Flow Distribution
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
article

Reliability improvement of distribution networks through optimal recloser placement considering photovoltaic resource allocation and sizing with protection coordination constraints

Hossein Lotfi, Mohammad Ebrahim Hajiabadi, Reza Tarsa, Hossein Ramezani et al.
3 links
Scientific Reports
Optimal Power Flow Distribution
article

Reliability improvement of distribution networks through optimal recloser placement considering photovoltaic resource allocation and sizing with protection coordination constraints

Hossein Lotfi, Mohammad Ebrahim Hajiabadi, Reza Tarsa, Hossein Ramezani, Majid Baghaei Nejad
article en

Abstract

This study presents an integrated optimization framework for the optimal placement of reclosers and the simultaneous determination of the location and capacity of photovoltaic (PV) units in distribution networks. Unlike conventional approaches that treat the placement of protection devices and PV allocation as separate planning problems, the proposed method addresses both problems simultaneously and evaluates the impact of PV integration on protection performance and network reliability. Within this framework, recloser placement aims to improve reliability indices, including SAIFI, SAIDI, and ENS, while the locations of PV units and the maximum hosting capacity are determined subject to network voltage constraints. In addition, the coordination constraint between the recloser and cut-out fuse is incorporated into the objective function as a penalty term to ensure proper protection coordination and maintain the fuse-saving strategy. The optimization problem is solved using a search algorithm, and the proposed method is evaluated on the IEEE 33-bus test system. In Scenario 2, Bus 29 is identified as the optimal location for a PV unit with a capacity equivalent to 70% of the total network load, resulting in an improved voltage profile. In Scenario 3, with the recloser optimally placed on Line 1, the ENS, SAIFI, and SAIDI values are 36.82 (MWh/yr), 5.58 (int/cus/yr) and 9.12 (h/cus/yr), respectively. Furthermore, the short-circuit analysis of faults downstream of the cut-out fuses confirms that the recloser–fuse coordination constraint is satisfied both with and without PV integration. The results demonstrate that the proposed framework can simultaneously optimize recloser placement and PV allocation while maintaining proper protection coordination and the fuse-saving strategy. It also enables an increase in PV hosting capacity subject to voltage constraints and improves network reliability.

Scientific Reports
Hakim Sabzevari University (IR)
Industry, innovation and infrastructure, Affordable and clean energy
Optimal Power Flow Distribution
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Laika access coming soon