Physics-Guided Graph-Temporal Learning for Power-Grid Stability Assessment and Risk Source Localization

Transient stability assessment must identify instability and its likely sources despite incomplete and delayed phasor measurement unit (PMU) data. This study develops a physics-guided graph-temporal framework that jointly predicts stability margins, instability types, risk sources, and line fault positions. A physical risk prior derived from differential-algebraic equations aggregates adverse scenarios through conditional value at risk and is fused with measurement-based source probabilities. A graph attention encoder and causal temporal convolution capture spatial and temporal dependencies, with PMU availability and elapsed-time indicators representing measurement degradation. Auxiliary algebraic power balance consistency guides training, while probability calibration and conformal prediction support confidence-based decisions. On the grouped 39-bus test set, rotor-angle and voltage balanced accuracies reached 99.22% and 98.86%, respectively, and Top-1 source localization accuracy reached 96.32%, 1.54 percentage points above the graph-temporal reference. The mean expected calibration error was 0.91%, and nominal 95% source sets achieved 95.40% empirical coverage with 1.42 candidates on average; coverage under 30% PMU loss was 94.62%. Under 30% PMU-channel loss and a six-sample delay, balanced accuracy was 97.31%, compared with 95.08% without measurement quality indicators. After retraining on an independent 68-bus system, rotor-angle balanced accuracy and Top-1 localization accuracy reached 98.37% and 92.68%, respectively. Model-only 95th-percentile latency was 21.8 ms for a single model and 58.9 ms for the five-model ensemble. The evaluated simulations quantify joint prediction accuracy, empirical coverage, and computational cost under topology and measurement variation.

Authors

Institutions

Publication Details

Journal
Processes
Published
2026-11-20
DOI
https://doi.org/10.3390/pr14223738
Primary Topic
Power System Optimization and Stability
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
article

Physics-Guided Graph-Temporal Learning for Power-Grid Stability Assessment and Risk Source Localization

Ruhai Hao, Zhen Niu, Tang Wen, Quanmao Li et al.
2 links
Processes
Power System Optimization and Stability
article

Physics-Guided Graph-Temporal Learning for Power-Grid Stability Assessment and Risk Source Localization

Ruhai Hao, Zhen Niu, Tang Wen, Quanmao Li, Tao Niu, Sibo Cheng
article en

Abstract

Transient stability assessment must identify instability and its likely sources despite incomplete and delayed phasor measurement unit (PMU) data. This study develops a physics-guided graph-temporal framework that jointly predicts stability margins, instability types, risk sources, and line fault positions. A physical risk prior derived from differential-algebraic equations aggregates adverse scenarios through conditional value at risk and is fused with measurement-based source probabilities. A graph attention encoder and causal temporal convolution capture spatial and temporal dependencies, with PMU availability and elapsed-time indicators representing measurement degradation. Auxiliary algebraic power balance consistency guides training, while probability calibration and conformal prediction support confidence-based decisions. On the grouped 39-bus test set, rotor-angle and voltage balanced accuracies reached 99.22% and 98.86%, respectively, and Top-1 source localization accuracy reached 96.32%, 1.54 percentage points above the graph-temporal reference. The mean expected calibration error was 0.91%, and nominal 95% source sets achieved 95.40% empirical coverage with 1.42 candidates on average; coverage under 30% PMU loss was 94.62%. Under 30% PMU-channel loss and a six-sample delay, balanced accuracy was 97.31%, compared with 95.08% without measurement quality indicators. After retraining on an independent 68-bus system, rotor-angle balanced accuracy and Top-1 localization accuracy reached 98.37% and 92.68%, respectively. Model-only 95th-percentile latency was 21.8 ms for a single model and 58.9 ms for the five-model ensemble. The evaluated simulations quantify joint prediction accuracy, empirical coverage, and computational cost under topology and measurement variation.

ProcessesVol. 14(22)
Chongqing University (CN), State Grid Corporation of China (China) (CN)
Affordable and clean energy, Industry, innovation and infrastructure
Power System Optimization and Stability
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Laika access coming soon
Physics-Guided Graph-Temporal Learning for Power-Grid Stability Assessment and Risk Source Localization — Ruhai Hao, Zhen Niu, et al. · Processes (2026) | TGRS Research Map | TGRS