Active and Reactive Power Loss Minimization in Nigeria 330kV Transmission Network Using Unified Power Flow Controller (UPFC)
The Nigerian 330kV transmission network experiences excessive active and reactive power losses due to transmission congestion, poor voltage regulation, and inadequate reactive power compensation. This paper presents the application of Unified Power Flow Controller (UPFC) for minimizing transmission losses and improving voltage stability in the Nigeria 330kV integrated transmission system. The network was modeled using ETAP and analyzed using a modified Newton-Raphson load flow algorithm. Simulation results showed that active power losses reduced from 90.30 MW to 35.10 MW while reactive power losses reduced from 53.30 MVAR to 31.90 MVAR after UPFC installation. Voltage profiles across weak buses improved significantly within statutory operational limits. The study demonstrates that UPFC can effectively improve transmission efficiency, reduce congestion, and enhance reliability of the Nigerian power grid.
Authors
- G.A James
- D.I Bayem
- J.I Sozaowei
- J.D Peletiri
- C.O Uloh
Institutions
- Nigeria Maritime University (NG)
Publication Details
- Journal
- Zenodo (CERN European Organization for Nuclear Research)
- Published
- 2026-11-19
- DOI
- https://doi.org/10.5281/zenodo.24358954
- Primary Topic
- Power System Optimization and Stability
- Type
- article
- Field-Weighted Citation Impact
- 0.00