Mitigation of DC-link ripples in smart converters under asymmetric grid conditions via stationary-frame dual-vector control

Asymmetric grid faults induce second-order harmonics in the DC-link voltage of three-phase AC/DC converters, leading to increased capacitor stress, reduced power quality, and compromised system stability. While sequence-decomposition-based control strategies effectively mitigate these effects, their practical adoption is often hindered by the computational overhead of synchronous reference frame transformations. Here, we propose and validate a Dual-Vector Current Control (DVCC) scheme operating primarily in the stationary reference frame for current regulation and reference generation, while employing minimal rotational transformations for sequence extraction. The control architecture employs a parallel arrangement of resonant filters to extract positive- and negative-sequence components, coupled with a notch-filter-based harmonic isolation stage to eliminate 100 Hz ripple without compromising transient response. Through analytical modeling and time-domain simulations under balanced and severely unbalanced grid conditions (voltage sag down to 0.85 p.u.), we demonstrate that under grid voltage sags down to 0.85 p.u., the proposed controller achieves a 92% reduction in DC-link voltage ripple compared to conventional PI control, and maintains input current total harmonic distortion below 7% under moderate unbalanced conditions (15% voltage sag) and below 3% under balanced conditions. Under severe single-phase loss (100% sag), THD increases to 37%, highlighting current limitations and the need for derating strategies. The bidirectional power transfer capability is preserved during fault transients, with settling times under 50 ms. These findings establish DVCC as a computationally efficient and robust alternative for grid-interfaced converters in distributed generation, electric vehicle charging, and microgrid applications, offering a practical pathway to enhanced grid resilience with minimal hardware modifications.

Authors

Institutions

Publication Details

Journal
Scientific Reports
Published
2026-11-19
DOI
https://doi.org/10.1038/s41598-026-80922-2
Primary Topic
Power Quality and Harmonics
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
article

Mitigation of DC-link ripples in smart converters under asymmetric grid conditions via stationary-frame dual-vector control

Faouzi Bacha, Marwa Ben Slimene, Mohamed Arbi Khlifi, Faouzi Tlili
Scientific Reports
Power Quality and Harmonics
article

Mitigation of DC-link ripples in smart converters under asymmetric grid conditions via stationary-frame dual-vector control

Faouzi Bacha, Marwa Ben Slimene, Mohamed Arbi Khlifi, Faouzi Tlili
article en

Abstract

Asymmetric grid faults induce second-order harmonics in the DC-link voltage of three-phase AC/DC converters, leading to increased capacitor stress, reduced power quality, and compromised system stability. While sequence-decomposition-based control strategies effectively mitigate these effects, their practical adoption is often hindered by the computational overhead of synchronous reference frame transformations. Here, we propose and validate a Dual-Vector Current Control (DVCC) scheme operating primarily in the stationary reference frame for current regulation and reference generation, while employing minimal rotational transformations for sequence extraction. The control architecture employs a parallel arrangement of resonant filters to extract positive- and negative-sequence components, coupled with a notch-filter-based harmonic isolation stage to eliminate 100 Hz ripple without compromising transient response. Through analytical modeling and time-domain simulations under balanced and severely unbalanced grid conditions (voltage sag down to 0.85 p.u.), we demonstrate that under grid voltage sags down to 0.85 p.u., the proposed controller achieves a 92% reduction in DC-link voltage ripple compared to conventional PI control, and maintains input current total harmonic distortion below 7% under moderate unbalanced conditions (15% voltage sag) and below 3% under balanced conditions. Under severe single-phase loss (100% sag), THD increases to 37%, highlighting current limitations and the need for derating strategies. The bidirectional power transfer capability is preserved during fault transients, with settling times under 50 ms. These findings establish DVCC as a computationally efficient and robust alternative for grid-interfaced converters in distributed generation, electric vehicle charging, and microgrid applications, offering a practical pathway to enhanced grid resilience with minimal hardware modifications.

Scientific Reports
Tunis University (TN), University of Ha'il (SA), National Engineering School of Tunis (TN), Islamic University of Madinah (SA), National Institute of Applied Science and Technology (TN), ENSIT (TN)
Power Quality and Harmonics
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Laika access coming soon