Numerical and Experimental Analysis of Pressure Loss in Cylindrical Air Duct
This study investigates the pressure loss in ventilation ducts by experimental measurements and numerical simulations in order to improve the accuracy of calculations in the design of ventilation systems. The experiments were conducted in a cylindrical duct with a diameter of 100 mm and a length of 1.5 m on the PAXP-VV-K “Ventilation System Testing” laboratory stand. The air velocity was varied in the range of 2.3–3.8 m/s (Re = 1.5×104–2.5×104), and the pressure drop was measured using differential manometers and pressure sensors, achieving high repeatability (standard deviation < 3 %; U(ΔP) = 11–19 %, k = 2). Numerical modeling was performed in the COMSOL Multiphysics program using the Realizable k-ε turbulence model. The measured loss was 4.5–8.5 Pa, whereas friction theory gives 1.4–3.3 Pa and the CFD simulation 2.6–3.8 Pa, i.e. the CFD values are 50–58 % lower than the measured ones. The discrepancy exceeds the standard measurement uncertainty by a factor of 7–10, so the model does not satisfy the ASME V&V 20 validation criterion; the excess loss (Ktot − λl/d ≈ 0.5–0.65) is of the magnitude of local losses in the measured path.