Assessment of Performance Ratio Variation in a 225 kWp Rooftop PV System Exposed to Industrial Fly Ash at PT Jaya Energi
This study evaluates monthly monitoring data from a 225 kWp grid-connected rooftop photovoltaic (PV) system at PT Jaya Energi, an industrial facility where boiler-derived fly ash may contribute to module soiling. Data from Huawei FusionSolar were analyzed for September-December 2025 and May-August 2026. January-April 2026 was excluded from the comparison because frequent rainfall and cloud cover could affect irradiance and remove accumulated dust. The recorded monthly Performance Ratio (PR) ranged from 54.9% to 60.3% during September-December 2025 and from 46.8% to 54.4% during May-August 2026. Within the latter period, PR decreased from 54.4% in May to 46.8% in August, a reduction of 7.6 percentage points (13.97% relative to May). This trend indicates lower recorded system performance, but it cannot be attributed exclusively to fly-ash soiling because direct soiling measurements and controlled clean/soiled comparisons were unavailable. The daily energy log recorded 0.00 kWh fed to the grid on each listed date, this supports zero recorded daily export but does not prove that instantaneous reverse power was absent at all times. The findings support further site-specific monitoring before a fixed cleaning interval or definitive zero-export performance claim is established.
Authors
- Pressa Perdana Surya Saputra (ORCID: https://orcid.org/0000-0002-8681-582X)
- Didik Nugroho
Publication Details
- Journal
- Andalasian International Journal of Applied Science Engineering and Technology
- Published
- 2026-11-17
- DOI
- https://doi.org/10.25077/aijaset.v6i3.378
- Primary Topic
- Photovoltaic System Optimization Techniques
- Type
- article
- Field-Weighted Citation Impact
- 0.00