Physically Interpretable Series Arc Fault Detection via Hilbert Transform-Derived Half-Cycle Energy Ratios and LightGBM

Series arc faults in low-voltage AC distribution systems pose a significant fire hazard but are difficult to detect because the fault current may remain below the operating thresholds of conventional circuit breakers and residual current devices. This paper proposes a physics-guided and lightweight detection framework that combines Hilbert-domain transient analysis, Half-Cycle Instantaneous Energy Ratio (HIER) modeling, and an edge-constrained LightGBM classifier. A test platform compliant with GB/T 31143 was constructed to acquire high-sampling-rate current signals from eight representative resistive, inductive, and nonlinear household loads under normal and series-arcing conditions. By treating each AC half-cycle as the fundamental modeling unit, three complementary HIER descriptors were developed to quantify localized energy bursts, out-of-band spectral dispersion, and frequency–amplitude instability. These descriptors were combined with analytic-signal envelope, instantaneous-frequency, and Teager–Kaiser energy features and aggregated over a 100 ms sliding window to form a compact 13-dimensional feature vector. On the reference test set, the proposed model achieved an accuracy of 98.52%, an arc-fault recall of 99.26%, an F1-score of 98.47%, and a ROC-AUC of 99.85%. Ablation experiments confirmed that the HIER descriptors provide complementary discriminative information, while SHAP analysis showed that the classifier decisions are consistent with the transient-energy and non-stationary characteristics of arc discharge. The complete model occupied approximately 0.53 MB, and tree-prefix pruning reduced its size to 194.2 KB while maintaining an F1-score above 0.98. These results demonstrate a favorable balance among detection performance, physical interpretability, and deployment efficiency for resource-constrained arc-fault detection devices.

Authors

Institutions

Publication Details

Journal
Energies
Published
2026-11-18
DOI
https://doi.org/10.3390/en19225564
Primary Topic
Electrical Fault Detection and Protection
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
article

Physically Interpretable Series Arc Fault Detection via Hilbert Transform-Derived Half-Cycle Energy Ratios and LightGBM

Yaping Du, Shoukang Luo, Chuanzhen Jia, Wenjing Sun et al.
6 links
Energies
Electrical Fault Detection and Protection
article

Physically Interpretable Series Arc Fault Detection via Hilbert Transform-Derived Half-Cycle Energy Ratios and LightGBM

Yaping Du, Shoukang Luo, Chuanzhen Jia, Wenjing Sun, Jiahui Lin, Zhe Li, Yang Li, Yubo Zhang
article en

Abstract

Series arc faults in low-voltage AC distribution systems pose a significant fire hazard but are difficult to detect because the fault current may remain below the operating thresholds of conventional circuit breakers and residual current devices. This paper proposes a physics-guided and lightweight detection framework that combines Hilbert-domain transient analysis, Half-Cycle Instantaneous Energy Ratio (HIER) modeling, and an edge-constrained LightGBM classifier. A test platform compliant with GB/T 31143 was constructed to acquire high-sampling-rate current signals from eight representative resistive, inductive, and nonlinear household loads under normal and series-arcing conditions. By treating each AC half-cycle as the fundamental modeling unit, three complementary HIER descriptors were developed to quantify localized energy bursts, out-of-band spectral dispersion, and frequency–amplitude instability. These descriptors were combined with analytic-signal envelope, instantaneous-frequency, and Teager–Kaiser energy features and aggregated over a 100 ms sliding window to form a compact 13-dimensional feature vector. On the reference test set, the proposed model achieved an accuracy of 98.52%, an arc-fault recall of 99.26%, an F1-score of 98.47%, and a ROC-AUC of 99.85%. Ablation experiments confirmed that the HIER descriptors provide complementary discriminative information, while SHAP analysis showed that the classifier decisions are consistent with the transient-energy and non-stationary characteristics of arc discharge. The complete model occupied approximately 0.53 MB, and tree-prefix pruning reduced its size to 194.2 KB while maintaining an F1-score above 0.98. These results demonstrate a favorable balance among detection performance, physical interpretability, and deployment efficiency for resource-constrained arc-fault detection devices.

EnergiesVol. 19(22)
Hong Kong Polytechnic University (HK), Shenzhen Stock Exchange (CN), China Southern Power Grid (China) (CN)
Electrical Fault Detection and Protection
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Laika access coming soon