A hybrid biorthogonal wavelet and superimposed current scheme for fast fault detection and classification on a 400 kV, 400 km transmission line

Long extra-high-voltage lines need protection that detects and types a fault within milliseconds. This paper proposes a two-stage relaying principle for a 400 kV, 50 Hz, 400 km transmission line. A level 1 biorthogonal (bior5.5) wavelet transform of relay currents captures the 5--10 kHz fault transient and raises the trip flag, after which half cycle RMS values of the superimposed phase and residual currents identify the faulted phases and any earth involvement. A MATLAB/Simulink model produced 462 fault records, covering eleven fault types, seven distances from 50 to 350 km and six fault resistances from 10 to 60~$\Omega$, plus one healthy record. Thresholds were fitted on part of the data and tested on unseen resistances or distances. Every fault was detected without a spurious trip, with mean delays of 0.27--1.50 ms that follow the wave travel time. All withheld faults were typed correctly when the identical ABC and ABCG faults form one class (90.9--91.0\% with eleven classes). The ground mode was found to dominate the high frequency transient of earth faults, which limits phase selection by the wavelet alone. The superimposed current stage stayed fully accurate down to 20 dB SNR, whereas the wavelet trigger needed about 60 dB.

Authors

Institutions

Publication Details

Journal
Research Square
Published
2026-11-18
DOI
https://doi.org/10.21203/rs.3.rs-11398011/v1
Primary Topic
Power Systems Fault Detection
Type
preprint
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
preprint

A hybrid biorthogonal wavelet and superimposed current scheme for fast fault detection and classification on a 400 kV, 400 km transmission line

Soma Deb, Abhay Yadav
Research Square
Power Systems Fault Detection
preprint

A hybrid biorthogonal wavelet and superimposed current scheme for fast fault detection and classification on a 400 kV, 400 km transmission line

Soma Deb, Abhay Yadav
preprint en

Abstract

Long extra-high-voltage lines need protection that detects and types a fault within milliseconds. This paper proposes a two-stage relaying principle for a 400 kV, 50 Hz, 400 km transmission line. A level 1 biorthogonal (bior5.5) wavelet transform of relay currents captures the 5--10 kHz fault transient and raises the trip flag, after which half cycle RMS values of the superimposed phase and residual currents identify the faulted phases and any earth involvement. A MATLAB/Simulink model produced 462 fault records, covering eleven fault types, seven distances from 50 to 350 km and six fault resistances from 10 to 60~$\Omega$, plus one healthy record. Thresholds were fitted on part of the data and tested on unseen resistances or distances. Every fault was detected without a spurious trip, with mean delays of 0.27--1.50 ms that follow the wave travel time. All withheld faults were typed correctly when the identical ABC and ABCG faults form one class (90.9--91.0\% with eleven classes). The ground mode was found to dominate the high frequency transient of earth faults, which limits phase selection by the wavelet alone. The superimposed current stage stayed fully accurate down to 20 dB SNR, whereas the wavelet trigger needed about 60 dB.

Research Square
Sharda University (IN)
Power Systems Fault Detection
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Laika access coming soon