Integrated Insulation Coordination for Pollution- and Lightning-Exposed Medium-Voltage Distribution Networks

Medium-voltage overhead distribution networks are exposed to atmospheric overvoltages and environmental pollution that can compromise external insulation performance. This paper proposes an integrated methodology for insulation coordination, surge-arrester verification, and identification of insulation design deficiencies under specified operating and environmental conditions. The methodology combines IEC 60071 and IEC 60815 requirements with electrical simulations performed in DIgSILENT PowerFactory using the IEEE 34-node distribution feeder. At Bus 832, the simulated representative electrical stresses were 18.462 kV RMS for temporary overvoltage, 35.533 kV peak for slow-front overvoltage, and 63.942 kV peak for fast-front overvoltage. After applying the corresponding coordination and atmospheric correction factors, the required withstand voltages remained below the selected standardized insulation levels of 70 kV RMS and 145 kV peak, with a commercial equipment rating of 150 kV BIL considered separately. The 18 kV surge arrester, with a maximum continuous operating voltage of 15.3 kV, satisfied the evaluated electrical requirements. Its simulated residual voltage differed by 0.247% from the catalog reference value, confirming numerical consistency at the selected operating point. Under the assumed Quito reference altitude and pollution correction factors, the ANSI 56-3 insulator, with a creepage distance of 533 mm, satisfied the requirements for pollution severity class a but exhibited a 114.2 mm deficit for class b. Furthermore, the simulated phase-to-ground fault resulted in the interruption of 83.09% of the feeder’s initial active power. The main contribution is a traceable procedure that distinguishes electrical coordination compliance from environmental insulation deficiencies, enabling targeted mitigation while preserving adequately coordinated components. The identified creepage-distance deficiency is conditional on the assumed pollution severity, and reductions in flashover occurrence and reliability indices require subsequent field-data validation.

Authors

Publication Details

Journal
Eng—Advances in Engineering
Published
2026-11-18
DOI
https://doi.org/10.3390/eng7110658
Primary Topic
High voltage insulation and dielectric phenomena
Type
article
Field-Weighted Citation Impact
0.00

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
article

Integrated Insulation Coordination for Pollution- and Lightning-Exposed Medium-Voltage Distribution Networks

Diego Francisco Carrión, Manuel Jaramillo, Danny Cuñas
Eng—Advances in Engineering
High voltage insulation and dielectric phenomena
article

Integrated Insulation Coordination for Pollution- and Lightning-Exposed Medium-Voltage Distribution Networks

Diego Francisco Carrión, Manuel Jaramillo, Danny Cuñas
article en

Abstract

Medium-voltage overhead distribution networks are exposed to atmospheric overvoltages and environmental pollution that can compromise external insulation performance. This paper proposes an integrated methodology for insulation coordination, surge-arrester verification, and identification of insulation design deficiencies under specified operating and environmental conditions. The methodology combines IEC 60071 and IEC 60815 requirements with electrical simulations performed in DIgSILENT PowerFactory using the IEEE 34-node distribution feeder. At Bus 832, the simulated representative electrical stresses were 18.462 kV RMS for temporary overvoltage, 35.533 kV peak for slow-front overvoltage, and 63.942 kV peak for fast-front overvoltage. After applying the corresponding coordination and atmospheric correction factors, the required withstand voltages remained below the selected standardized insulation levels of 70 kV RMS and 145 kV peak, with a commercial equipment rating of 150 kV BIL considered separately. The 18 kV surge arrester, with a maximum continuous operating voltage of 15.3 kV, satisfied the evaluated electrical requirements. Its simulated residual voltage differed by 0.247% from the catalog reference value, confirming numerical consistency at the selected operating point. Under the assumed Quito reference altitude and pollution correction factors, the ANSI 56-3 insulator, with a creepage distance of 533 mm, satisfied the requirements for pollution severity class a but exhibited a 114.2 mm deficit for class b. Furthermore, the simulated phase-to-ground fault resulted in the interruption of 83.09% of the feeder’s initial active power. The main contribution is a traceable procedure that distinguishes electrical coordination compliance from environmental insulation deficiencies, enabling targeted mitigation while preserving adequately coordinated components. The identified creepage-distance deficiency is conditional on the assumed pollution severity, and reductions in flashover occurrence and reliability indices require subsequent field-data validation.

Eng—Advances in EngineeringVol. 7(11)
Universidad Politécnica Salesiana del Ecuador
Industry, innovation and infrastructure, Affordable and clean energy
High voltage insulation and dielectric phenomena
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Laika access coming soon