Delay-Compensated Complementary Coordination of Grid-Forming and Grid-Following Energy Storage for Primary Frequency Regulation with an Identification-Based Frequency-Security Guard

Abstract Converter-interfaced energy storage now carries a growing share of primary frequency regulation, but its two control modes fail in opposite ways: grid-following (GFL) units can be rated large yet act through a phase-locked loop and a measurement delay, while grid-forming (GFM) units act at once but are small and tightly current limited. This paper proposes a predictive complementary split with a robust frequency-security guard (PCS-RG). When grid connected, the GFM unit supplies virtual inertia and a wash-out droop while the GFL unit applies an event-triggered, front-loaded droop to a frequency predicted from the rate of change of frequency (RoCoF), which offsets the GFL delay without forecasting the nadir. After islanding the GFM unit follows an energy-aware trajectory of inertia, transient droop and ramped steady droop, and a guard identifies the power imbalance and the governor droop online, raising the droop only when the steady-state limit is at risk; if synchronous machines remain, the GFL unit re-locks and carries that droop. On a three-area average-system-frequency model the scheme lowers the nadir by 9.6% at unchanged state of charge, keeps it 33% lower at 300 to 400 ms of delay, cuts islanded RoCoF by 30% and removes every steady-state violation in 120 randomised islands, where a deviation-scheduled benchmark violates in 48% of cases. A validation on the IEEE 10-machine 39-bus system with machine dynamics and explicit converter current limits gives the benchmark nadir with 41% less GFM peak power after a generator trip and, in a 15-bus island with a 548 MW deficit, a 0.161 Hz nadir and a 0.068 Hz settling deviation where the benchmark saturates its converter, exhausts it after 15 s and settles outside a 0.12 Hz limit.

Authors

Institutions

Publication Details

Journal
Research Square
Published
2026-11-17
DOI
https://doi.org/10.21203/rs.3.rs-11084433/v1
Primary Topic
Microgrid Control and Optimization
Type
preprint
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
preprint

Delay-Compensated Complementary Coordination of Grid-Forming and Grid-Following Energy Storage for Primary Frequency Regulation with an Identification-Based Frequency-Security Guard

Muzeeb Khan Patan
3 links
Research Square
Microgrid Control and Optimization
preprint

Delay-Compensated Complementary Coordination of Grid-Forming and Grid-Following Energy Storage for Primary Frequency Regulation with an Identification-Based Frequency-Security Guard

Muzeeb Khan Patan
preprint en

Abstract

Abstract Converter-interfaced energy storage now carries a growing share of primary frequency regulation, but its two control modes fail in opposite ways: grid-following (GFL) units can be rated large yet act through a phase-locked loop and a measurement delay, while grid-forming (GFM) units act at once but are small and tightly current limited. This paper proposes a predictive complementary split with a robust frequency-security guard (PCS-RG). When grid connected, the GFM unit supplies virtual inertia and a wash-out droop while the GFL unit applies an event-triggered, front-loaded droop to a frequency predicted from the rate of change of frequency (RoCoF), which offsets the GFL delay without forecasting the nadir. After islanding the GFM unit follows an energy-aware trajectory of inertia, transient droop and ramped steady droop, and a guard identifies the power imbalance and the governor droop online, raising the droop only when the steady-state limit is at risk; if synchronous machines remain, the GFL unit re-locks and carries that droop. On a three-area average-system-frequency model the scheme lowers the nadir by 9.6% at unchanged state of charge, keeps it 33% lower at 300 to 400 ms of delay, cuts islanded RoCoF by 30% and removes every steady-state violation in 120 randomised islands, where a deviation-scheduled benchmark violates in 48% of cases. A validation on the IEEE 10-machine 39-bus system with machine dynamics and explicit converter current limits gives the benchmark nadir with 41% less GFM peak power after a generator trip and, in a 15-bus island with a 548 MW deficit, a 0.161 Hz nadir and a 0.068 Hz settling deviation where the benchmark saturates its converter, exhausts it after 15 s and settles outside a 0.12 Hz limit.

Research Square
University of Technology and Applied Sciences, Muscat (OM), University of Technology and Applied Sciences (OM)
Affordable and clean energy, Industry, innovation and infrastructure
Microgrid Control and Optimization
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Laika access coming soon