Field Calibration of Low-Cost SHT20 and BH1750 Sensors for Microclimate Monitoring in a Tropical Greenhouse: Effects of Calibration Range and Transmission Interval

Low-cost sensor nodes now drive climate control in many tropical greenhouses, yet their accuracy is usually taken from datasheets rather than tested across the conditions in which a controller acts. Here, three ESP32 nodes with SHT20 temperature and relative humidity (RH) sensors and BH1750 light sensors were calibrated and validated against reference instruments in a fan-and-pad cooled greenhouse in Indonesia and followed through 1458 paired readings per quantity at three times of day. The effect of the transmission interval was isolated by subsampling 1 min series at 5 and 10 min, which holds the weather constant between intervals. Before correction the sensors read up to 2.4 °C warm and 8.5 % RH wet, and a linear correction fitted on a two-hour late-afternoon window brought the validation root-mean-square error (RMSE) to 0.34 °C–0.75 °C and 1.1 %–2.6 % RH, within the stated accuracy of reference instruments that are not traceable; these figures measure agreement with that reference, not absolute accuracy. In the field, 83 % of temperature readings agreed with the reference to within ± 1 °C inside the calibrated range but 38 % above 39.3 °C, mostly at midday, and the share of humidity readings within ± 5 % RH fell from 92 % to 36 % above 65 % RH in the morning. In 18 hourly windows, a 10 min interval changed hourly means of temperature and humidity by no more than 0.22 °C and 0.91 % RH, but missed hourly illuminance peaks by up to 19.9 klx under rapidly varying light. In this greenhouse, most of the disagreement with the reference arose outside the calibration window, which suggests, though this was not tested, that field calibrations of low-cost nodes should span the midday heat and the morning humidity at which cooling decisions are made.

Authors

Institutions

Publication Details

Journal
Green and Sustainable Environments
Published
2026-11-17
DOI
https://doi.org/10.62755/gsenv.2026.09
Primary Topic
Greenhouse Technology and Climate Control
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
article

Field Calibration of Low-Cost SHT20 and BH1750 Sensors for Microclimate Monitoring in a Tropical Greenhouse: Effects of Calibration Range and Transmission Interval

Kisna Pertiwi, Zunanik Mufidah, Mahardika Priya Tumanggor
2 links
Green and Sustainable Environments
Greenhouse Technology and Climate Control
article

Field Calibration of Low-Cost SHT20 and BH1750 Sensors for Microclimate Monitoring in a Tropical Greenhouse: Effects of Calibration Range and Transmission Interval

Kisna Pertiwi, Zunanik Mufidah, Mahardika Priya Tumanggor
article en

Abstract

Low-cost sensor nodes now drive climate control in many tropical greenhouses, yet their accuracy is usually taken from datasheets rather than tested across the conditions in which a controller acts. Here, three ESP32 nodes with SHT20 temperature and relative humidity (RH) sensors and BH1750 light sensors were calibrated and validated against reference instruments in a fan-and-pad cooled greenhouse in Indonesia and followed through 1458 paired readings per quantity at three times of day. The effect of the transmission interval was isolated by subsampling 1 min series at 5 and 10 min, which holds the weather constant between intervals. Before correction the sensors read up to 2.4 °C warm and 8.5 % RH wet, and a linear correction fitted on a two-hour late-afternoon window brought the validation root-mean-square error (RMSE) to 0.34 °C–0.75 °C and 1.1 %–2.6 % RH, within the stated accuracy of reference instruments that are not traceable; these figures measure agreement with that reference, not absolute accuracy. In the field, 83 % of temperature readings agreed with the reference to within ± 1 °C inside the calibrated range but 38 % above 39.3 °C, mostly at midday, and the share of humidity readings within ± 5 % RH fell from 92 % to 36 % above 65 % RH in the morning. In 18 hourly windows, a 10 min interval changed hourly means of temperature and humidity by no more than 0.22 °C and 0.91 % RH, but missed hourly illuminance peaks by up to 19.9 klx under rapidly varying light. In this greenhouse, most of the disagreement with the reference arose outside the calibration window, which suggests, though this was not tested, that field calibrations of low-cost nodes should span the midday heat and the morning humidity at which cooling decisions are made.

Green and Sustainable EnvironmentsVol. 1(2)
Sumatera Institute of Technology (ID)
Greenhouse Technology and Climate Control
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Laika access coming soon