Edge-Driven Collaborative Control for Harmonic Mitigation in Distributed Shipboard Multi-Module Converter Systems
Parallel multi-module converters in shipboard power systems suffer from Total Harmonic Distortion (THD), and centralized control is limited by response delay, single-point failure and poor adaptability. This paper proposes an edge-intelligence-driven collaborative control scheme that combines layered feedback, a state machine within a layered edge-central architecture, dynamic thresholding and local self-healing, so that local autonomy is corrected by global feedback. On a five-module platform, compared with centralized control, the edge-based algorithm reduces the mean THD by 46% (5.2% to 2.8%) and the maximum observed response time by 47% (27.4 ms to 14.6 ms), and lowers the peak energy of module 1 by 53.9% (from 2.32 to 1.07 per unit), although the peak energy of module 2 rises from 1.67 to 2.89 per unit. THD remains bounded under load transients and a communication fault at one module (transient peak 4.1%, recovering to 2.9% within 100 ms).