Data Centre Waste Heat Utilisation: A Closed-Loop Thermal Integration with Jacketed CSTR Systems
AI data centres in Sydney use large amounts of electricity for GPU cooling, yet the resulting low-grade heat is released to the surrounding and wasted. The proposed system sized a closed-loop glycol-water recovery system using thermal camera measurements, hierarchical scaling, SOLIDWORKS CFD, and standard conduction and convection heat-transfer equations. For a representative 16,000-GPU hyperscale facility (NVIDIA H100), about 9.25 MW of waste heat is recoverable, with coolant heated from 20 °C to roughly 37 °C per coolant distribution pipe and only approximately 755 W of heat lost over 199 m of insulated stainless-steel pipe. The heat is delivered to the jacket of a continuous stirred-tank reactor (CSTR) in a co-located manufacturing plant. Switching from air to liquid cooling at this scale drops annual cooling cost from about 51 to 30 million AUD and annual CO₂ emissions from 78.4 to 7.84 million kg. Payback is under one year.
Publication Details
- Journal
- The Sydney Journal of Interdisciplinary Engineering
- Published
- 2026-11-18
- DOI
- https://doi.org/10.30722/t29tnb69
- Primary Topic
- Thermodynamic and Exergetic Analyses of Power and Cooling Systems
- Type
- article
- Field-Weighted Citation Impact
- 0.00