Electrothermal Failure Mechanism of Multi-Finger Contacts in a Disconnector Under Foundation-Induced Displacement

To clarify the electrothermal failure of fixed contacts in a 363 kV three-phase five-column disconnector, field inspection, circuit-resistance tests, contact-mechanical modeling, finger-level resistance calculation, and electrothermal simulation were combined. The fault side had approximately 10 mm settlement and 51 mm horizontal displacement. Unserved contacts remained at 81–83 μΩ, whereas field-served contacts showed displacement-sensitive, non-monotonic resistance changes. A finite element model of 24 contact fingers with assembly-induced prestress was developed. Contact pressures were calculated under normal, settlement, and combined settlement—horizontal displacement conditions. Normal force was integrated over each contact area, and zero pressure denoted contact loss. The force, contact length, and equivalent contact width were used in a cylinder-on-flat model to calculate finger resistance. These resistances were connected in parallel and calibrated against the measured normal-state resistance of 83.57 μΩ. Settlement redistributed load from lower to upper fingers, while further horizontal displacement concentrated contact on one side; eastward displacement caused all bottom-row fingers to lose contact. Electrothermal simulation showed little temperature change while most fingers remained in contact, but temperatures exceeded 130 °C after bottom-row contact loss. Thus, total resistance can conceal local degradation, while load redistribution and current concentration increase Joule heating in remaining paths and explain burnout.

Authors

Institutions

Publication Details

Journal
Energies
Published
2026-11-17
DOI
https://doi.org/10.3390/en19225563
Primary Topic
Electrical Contact Performance and Analysis
Type
article
Field-Weighted Citation Impact
0.00

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
article

Electrothermal Failure Mechanism of Multi-Finger Contacts in a Disconnector Under Foundation-Induced Displacement

Bodong Chen, Hailong Wang, Jia Zhang, Kang Liu et al.
2 links
Energies
Electrical Contact Performance and Analysis
article

Electrothermal Failure Mechanism of Multi-Finger Contacts in a Disconnector Under Foundation-Induced Displacement

Bodong Chen, Hailong Wang, Jia Zhang, Kang Liu, Luyao Wang, Miao Wen, Tiancun Wu
article en

Abstract

To clarify the electrothermal failure of fixed contacts in a 363 kV three-phase five-column disconnector, field inspection, circuit-resistance tests, contact-mechanical modeling, finger-level resistance calculation, and electrothermal simulation were combined. The fault side had approximately 10 mm settlement and 51 mm horizontal displacement. Unserved contacts remained at 81–83 μΩ, whereas field-served contacts showed displacement-sensitive, non-monotonic resistance changes. A finite element model of 24 contact fingers with assembly-induced prestress was developed. Contact pressures were calculated under normal, settlement, and combined settlement—horizontal displacement conditions. Normal force was integrated over each contact area, and zero pressure denoted contact loss. The force, contact length, and equivalent contact width were used in a cylinder-on-flat model to calculate finger resistance. These resistances were connected in parallel and calibrated against the measured normal-state resistance of 83.57 μΩ. Settlement redistributed load from lower to upper fingers, while further horizontal displacement concentrated contact on one side; eastward displacement caused all bottom-row fingers to lose contact. Electrothermal simulation showed little temperature change while most fingers remained in contact, but temperatures exceeded 130 °C after bottom-row contact loss. Thus, total resistance can conceal local degradation, while load redistribution and current concentration increase Joule heating in remaining paths and explain burnout.

EnergiesVol. 19(22)
Shenyang Agricultural University (CN), State Grid Corporation of China (China) (CN)
Science and Technology Project of State Grid
Electrical Contact Performance and Analysis
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Laika access coming soon