Cooling tower frequency optimization and energy saving potential in a tobacco factory chiller plant with a fixed equipment combination

Tobacco manufacturing requires a continuous and stable cooling source for process air conditioning. Chiller-plant optimization must reduce refrigeration and heat-rejection electricity while preserving the established cooling service. In operating archives from industrial plants, however, tower frequency, condenser-water temperature and existing feedback actions often change together, so historical association alone does not identify the temperature response to a new frequency. This study addresses that problem for a tobacco factory chiller plant in Yangzhou by formulating a component energy balance for a fixed equipment combination and treating the unmeasured tower-frequency response as an explicit scenario parameter. The archive ending at 00:00 on 15 October 2026 yields 1372 disjoint windows; the primary combination provides 314 windows over 43 operating dates, divided into 279 fitting, 15 validation and 20 evaluation windows. With measured condenser inlet temperature, evaluation RMSE values are 11.24 kW for chiller power and 0.89 kW for tower power. Reducing three towers from 50 to 47.5 Hz gives a modeled fan-power credit of 4.14 kW; at loads of 2500–4500 kW, the corresponding break-even warming is 0.130–0.072 °C. Under four specified thermal-response scenarios, local optimization gives mean modeled credits of 0.55–10.50 kW, or 0.10%–1.95% of the accounting boundary, and the preferred direction changes with response intensity. The study quantifies the energy tradeoff and the temperature-response measurements required for a subsequent frequency-adjustment test; the scenario credits are not field-measured savings.

Authors

Institutions

Publication Details

Journal
Advances in Engineering Innovation
Published
2026-11-16
DOI
https://doi.org/10.54254/2977-3903/2026.39220
Primary Topic
Building Energy and Comfort Optimization
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
article

Cooling tower frequency optimization and energy saving potential in a tobacco factory chiller plant with a fixed equipment combination

Wang Ruan, Feng Zeng, Rui Rong, Yanqin Han et al.
1 links
Advances in Engineering Innovation
Building Energy and Comfort Optimization
article

Cooling tower frequency optimization and energy saving potential in a tobacco factory chiller plant with a fixed equipment combination

Wang Ruan, Feng Zeng, Rui Rong, Yanqin Han, Hehua Shao, Jing Wang, Hongyu Gu
article en

Abstract

Tobacco manufacturing requires a continuous and stable cooling source for process air conditioning. Chiller-plant optimization must reduce refrigeration and heat-rejection electricity while preserving the established cooling service. In operating archives from industrial plants, however, tower frequency, condenser-water temperature and existing feedback actions often change together, so historical association alone does not identify the temperature response to a new frequency. This study addresses that problem for a tobacco factory chiller plant in Yangzhou by formulating a component energy balance for a fixed equipment combination and treating the unmeasured tower-frequency response as an explicit scenario parameter. The archive ending at 00:00 on 15 October 2026 yields 1372 disjoint windows; the primary combination provides 314 windows over 43 operating dates, divided into 279 fitting, 15 validation and 20 evaluation windows. With measured condenser inlet temperature, evaluation RMSE values are 11.24 kW for chiller power and 0.89 kW for tower power. Reducing three towers from 50 to 47.5 Hz gives a modeled fan-power credit of 4.14 kW; at loads of 2500–4500 kW, the corresponding break-even warming is 0.130–0.072 °C. Under four specified thermal-response scenarios, local optimization gives mean modeled credits of 0.55–10.50 kW, or 0.10%–1.95% of the accounting boundary, and the preferred direction changes with response intensity. The study quantifies the energy tradeoff and the temperature-response measurements required for a subsequent frequency-adjustment test; the scenario credits are not field-measured savings.

Advances in Engineering InnovationVol. 17(12)
North China Electric Power University (CN), China Tobacco (CN)
Affordable and clean energy, Climate action, Industry, innovation and infrastructure
Building Energy and Comfort Optimization
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Laika access coming soon