Experimental Thermal–Hydraulic Evaluation of Continuous and Notched-Fin Liquid–Suction Heat Exchangers in an R407C Freezing System

Liquid–suction heat exchangers subcool the liquid line of a refrigeration cycle and protect the compressor, but in small freezing units their duty is usually limited by weak heat transfer on the suction-vapor side. This study adds a longitudinal fin on that side and examines whether notching the fin improves it further. In each of three exchangers, a copper fin 10 mm high and 1 mm thick was brazed under the liquid line and inserted through a slot into the suction line over a 600 mm contact length. The fin was continuous or carried 9 or 17 notches, each 5 mm wide and 5 mm deep. Each exchanger was installed in turn in an R407C freezing system serving a 15 m³ cold room and compared with the same cycle without an exchanger at evaporating temperatures from −25 to −10 °C. The effectiveness rose with the number of notches, reaching 0.14, 0.28 and 0.38 at −10 °C, although the notches removed up to 5.4% of the fin area. At −25 °C, the coefficient of performance increased from 2.59 to 2.80, 3.03 and 3.18, the refrigeration capacity of the 17-notch exchanger rose from 4.96 to 5.35 kW, and the compressor work fell by up to 12.4%. The metered daily energy use dropped by 5.7%, 7.3% and 10.4%. The cost was a higher suction-side pressure drop, which reached 7.6 kPa with 17 notches, so the notch density should be chosen against the suction pressure loss that the compressor can accept.

Authors

Institutions

Publication Details

Journal
International Journal of Scientific Research in Science Engineering and Technology
Published
2026-11-15
DOI
https://doi.org/10.32628/ijsrset2613601
Primary Topic
Refrigeration and Air Conditioning Technologies
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
article

Experimental Thermal–Hydraulic Evaluation of Continuous and Notched-Fin Liquid–Suction Heat Exchangers in an R407C Freezing System

Ayad Dawood Sulaiman
International Journal of Scientific Research in Science Engineering and Technology
Refrigeration and Air Conditioning Technologies
article

Experimental Thermal–Hydraulic Evaluation of Continuous and Notched-Fin Liquid–Suction Heat Exchangers in an R407C Freezing System

Ayad Dawood Sulaiman
article en

Abstract

Liquid–suction heat exchangers subcool the liquid line of a refrigeration cycle and protect the compressor, but in small freezing units their duty is usually limited by weak heat transfer on the suction-vapor side. This study adds a longitudinal fin on that side and examines whether notching the fin improves it further. In each of three exchangers, a copper fin 10 mm high and 1 mm thick was brazed under the liquid line and inserted through a slot into the suction line over a 600 mm contact length. The fin was continuous or carried 9 or 17 notches, each 5 mm wide and 5 mm deep. Each exchanger was installed in turn in an R407C freezing system serving a 15 m³ cold room and compared with the same cycle without an exchanger at evaporating temperatures from −25 to −10 °C. The effectiveness rose with the number of notches, reaching 0.14, 0.28 and 0.38 at −10 °C, although the notches removed up to 5.4% of the fin area. At −25 °C, the coefficient of performance increased from 2.59 to 2.80, 3.03 and 3.18, the refrigeration capacity of the 17-notch exchanger rose from 4.96 to 5.35 kW, and the compressor work fell by up to 12.4%. The metered daily energy use dropped by 5.7%, 7.3% and 10.4%. The cost was a higher suction-side pressure drop, which reached 7.6 kPa with 17 notches, so the notch density should be chosen against the suction pressure loss that the compressor can accept.

International Journal of Scientific Research in Science Engineering and TechnologyVol. 13(6)
Northern Technical University (IQ)
Refrigeration and Air Conditioning Technologies
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Laika access coming soon