Recirculating split air conditioning in shared offices: CO₂, airborne infection risk and the energy cost of adding fresh air

Many offices are cooled by split air conditioning units that recirculate room air but supply no outdoor air. This study models a 216 m³ shared office with eight occupants in south-east England, comparing split air conditioning alone with portable HEPA filtration and with outdoor air supply at 10 and 14 L/s per person. With split air conditioning alone and infiltration of 0.2 air changes per hour, mean CO₂ while occupied was 1,810 ppm, peaking at 2,561 ppm, and exceeded 1,500 ppm for 71% of occupied time. Supplying 10 L/s per person through a unit with heat recovery reduced mean CO₂ to 715 ppm and cut the modelled daily risk of airborne infection by 40–65%, for about £75 a year, or £9.3 per occupant. A portable HEPA unit gave the same reduction in infection risk at a third of the running cost but left CO₂ unchanged, so a CO₂ monitor would show no improvement. Without heat recovery, the same outdoor air cost 52% more to supply and nearly tripled the added emissions. Outdoor air at the regulatory minimum is inexpensive to provide, and air cleaning should be treated as an addition to it rather than a substitute.

Authors

Publication Details

Journal
Zenodo (CERN European Organization for Nuclear Research)
Published
2026-11-13
DOI
https://doi.org/10.5281/zenodo.24205294
Primary Topic
Infection Control and Ventilation
Type
preprint
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
preprint

Recirculating split air conditioning in shared offices: CO₂, airborne infection risk and the energy cost of adding fresh air

Naushad Ali
3 links
Zenodo (CERN European Organization for Nuclear Research)
Infection Control and Ventilation
preprint

Recirculating split air conditioning in shared offices: CO₂, airborne infection risk and the energy cost of adding fresh air

Naushad Ali
preprint en

Abstract

Many offices are cooled by split air conditioning units that recirculate room air but supply no outdoor air. This study models a 216 m³ shared office with eight occupants in south-east England, comparing split air conditioning alone with portable HEPA filtration and with outdoor air supply at 10 and 14 L/s per person. With split air conditioning alone and infiltration of 0.2 air changes per hour, mean CO₂ while occupied was 1,810 ppm, peaking at 2,561 ppm, and exceeded 1,500 ppm for 71% of occupied time. Supplying 10 L/s per person through a unit with heat recovery reduced mean CO₂ to 715 ppm and cut the modelled daily risk of airborne infection by 40–65%, for about £75 a year, or £9.3 per occupant. A portable HEPA unit gave the same reduction in infection risk at a third of the running cost but left CO₂ unchanged, so a CO₂ monitor would show no improvement. Without heat recovery, the same outdoor air cost 52% more to supply and nearly tripled the added emissions. Outdoor air at the regulatory minimum is inexpensive to provide, and air cleaning should be treated as an addition to it rather than a substitute.

Zenodo (CERN European Organization for Nuclear Research)
Climate action, Good health and well-being
Infection Control and Ventilation
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Laika access coming soon