Degradation- and Inventory-Aware Hierarchical Frequency Control of PEM Fuel Cells and Electrolyzers in Low-Inertia Microgrids
PEM fuel cells and electrolyzers can support frequency in low-inertia microgrids, but a switched-off unit needs time to start, every start–stop cycle degrades the stack, and a hydrogen chain with about 30% round-trip efficiency drains its tank even at zero net energy exchange. This paper proposes a degradation- and inventory-aware hierarchical frequency controller: a rate-aware tube model predictive control (MPC) power layer; a commitment layer that applies the classical ski-rental rule with break-even times derived from stack degradation and standby costs (commitment cost bounded by twice the offline optimum plus one start, excluding frequency performance); and a hydrogen-inventory layer that shifts the conventional-unit schedule to hold the tank level. On an electrochemical plant with a realistic information structure and 48 unseen test cases, the controller matches the frequency performance of a perfect-foresight commitment at 5% higher cost and reduces the integral absolute frequency error by 26% versus fuel-cell-only standby, 19% versus a tuned hold-time rule and 28–36% versus tuned PI, PID, fractional-order PID, fuzzy and MPC controllers. The gain grows with the electrolyzer start-up time and persists under random plant–model mismatch. Against a hold-time rule tuned on hour-long profiles, however, the frequency advantage is minimal; the remaining benefits are lower cost and the absence of cold electrolyzer onsets. Over ten days, the inventory layer keeps the tank within 1.09–1.29 kg; without it, the tank empties after 17–20 h.
Authors
- Cem Haydaroğlu (ORCID: https://orcid.org/0000-0003-0830-5530)
Institutions
- Dicle University (TR)
Publication Details
- Journal
- Energies
- Published
- 2026-11-13
- DOI
- https://doi.org/10.3390/en19225483
- Primary Topic
- Microgrid Control and Optimization
- Type
- article
- Field-Weighted Citation Impact
- 0.00