A Low-Cost Embedded System for Non-Technical Loss Detection in Low-Voltage Distribution Networks

A low-cost wireless embedded system was developed and evaluated for the local and real-time detection of non-technical losses caused by electrical bypasses in low-voltage service drops. The architecture consists of two ESP32-based measurement nodes equipped with PZEM-004T V3 modules and interconnected through ESP-NOW. Node A measures the electrical variables at the service connection point, whereas Node B acquires the billing-point variables, processes the received telemetry, and displays the operating status through a local web dashboard. The detection model incorporates the estimated resistive loss of the service drop and applies a current-dependent dynamic threshold to distinguish technical losses from unexplained power discrepancies. Measurement pairs are validated through sequence identification, timestamp-based synchronization, and wireless-link quality criteria before classification. The experimental campaign comprised 40 scenarios, including 20 controlled tests and 20 different residential service drops with conductor cross-sectional areas of 6 and 10 mm², lengths from 4 to 25 m, and different load profiles. Thirty-eight acquisitions satisfied the established quality criteria. The system obtained 9 true positives, 28 true negatives, 0 false positives, and 1 false negative, corresponding to an accuracy of 97.37%, sensitivity of 90.00%, specificity of 100.00%, and precision of 100.00%. The ESP-NOW link achieved an overall packet error rate of 0.79% and a mean transmission latency of 4.36 ms. The results show that technical-loss compensation and acquisition-quality control reduce false alerts under the evaluated high-load, transient, and nonlinear operating conditions.

Authors

Institutions

Publication Details

Journal
International Journal of Electrical and Electronics Engineering
Published
2026-11-13
DOI
https://doi.org/10.14445/23488379/ijeee-v13i10p108
Primary Topic
Electricity Theft Detection Techniques
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
article

A Low-Cost Embedded System for Non-Technical Loss Detection in Low-Voltage Distribution Networks

Jezzy James Huaman Rojas, Andy Quispe Mendoza, Cristhian Paolo Poma Mercado, Yordan Zosimo Cerron Armas
International Journal of Electrical and Electronics Engineering
Electricity Theft Detection Techniques
article

A Low-Cost Embedded System for Non-Technical Loss Detection in Low-Voltage Distribution Networks

Jezzy James Huaman Rojas, Andy Quispe Mendoza, Cristhian Paolo Poma Mercado, Yordan Zosimo Cerron Armas
article en

Abstract

A low-cost wireless embedded system was developed and evaluated for the local and real-time detection of non-technical losses caused by electrical bypasses in low-voltage service drops. The architecture consists of two ESP32-based measurement nodes equipped with PZEM-004T V3 modules and interconnected through ESP-NOW. Node A measures the electrical variables at the service connection point, whereas Node B acquires the billing-point variables, processes the received telemetry, and displays the operating status through a local web dashboard. The detection model incorporates the estimated resistive loss of the service drop and applies a current-dependent dynamic threshold to distinguish technical losses from unexplained power discrepancies. Measurement pairs are validated through sequence identification, timestamp-based synchronization, and wireless-link quality criteria before classification. The experimental campaign comprised 40 scenarios, including 20 controlled tests and 20 different residential service drops with conductor cross-sectional areas of 6 and 10 mm², lengths from 4 to 25 m, and different load profiles. Thirty-eight acquisitions satisfied the established quality criteria. The system obtained 9 true positives, 28 true negatives, 0 false positives, and 1 false negative, corresponding to an accuracy of 97.37%, sensitivity of 90.00%, specificity of 100.00%, and precision of 100.00%. The ESP-NOW link achieved an overall packet error rate of 0.79% and a mean transmission latency of 4.36 ms. The results show that technical-loss compensation and acquisition-quality control reduce false alerts under the evaluated high-load, transient, and nonlinear operating conditions.

International Journal of Electrical and Electronics EngineeringVol. 13(10)
Universidad Continental (PE)
Industry, innovation and infrastructure
Electricity Theft Detection Techniques
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Laika access coming soon