Ensuring HAPS Reliability in the Era of Systematic (Software) Failures: Multi-Level Validation of SCL Files
In modern highly automated power stations (HAPS) the hardware reliability is largely determined by hardware redundancy. However, the intro- duction of digital systems shifts the risk profi le, both for hardware and soft- ware. The Russian standard GOST R IEC 61508 provides a structured framework for addressing diff erent types of failures and clearly prescribes tailored mitigation strategies for each. While the software of microprocessor- based relay protection and automation (RPA) devices is developed according to the principles of Secure Software Development (SSD) and undergoes industry-specifi c validation, the confi guration SCL fi les defi ned by IEC 61850 lacks a systematic control framework. This paper argues that a multi-level au- tomated validation of SCL fi les based on IEC 61850-6-3:2025 and the Object Constraint Language (OCL) is the most eff ective countermeasure against such failures in HAPS in terms of reliability-to-cost ratio. A concept of levels L1–L6 is proposed, covering syntax, data semantics, communication integrity, and design rules. The paramount role of independent validation tools (FVT) in this new approach to ensuring HAPS reliability is also highlighted.
Authors
- A Atnishkin
- A Russanov
- S Shushpanov
- D Leontiev
Publication Details
- Journal
- Electric Power Transmission and Distribution
- Published
- 2026-11-12
- DOI
- https://doi.org/10.65209/2218-3116-2026-6-99-128-136
- Primary Topic
- Power Systems and Technologies
- Type
- article
- Field-Weighted Citation Impact
- 0.00