Design and Experimental Validation of an In-Service Self-Test for IGBT Turn-Off Capability in a 400 Hz Current-Limiting Device

A current-limiting device (CLD) on a 400 Hz shipboard bus protects its load by turning an IGBT path off and diverting the current into a reactor. An IGBT that has failed stuck-on keeps supplying the load and appears healthy, so the loss of turn-off capability can be found only by testing the path in service, without creating a fault current and with the single Hall sensor already installed. This paper designs and validates such a self-test. Short high-impedance pulses at 45° and 225° force a current-path transfer in each of the two anti-series IGBTs, whose transient current drop ratio is the decision metric; a three-of-four criterion and a current-dependent deferral rule confine verdicts to currents the measurement chain can resolve. On production units, no healthy resistive-load capture failed at or above 7.5 A (0 of 25), and all three captures with a jumper emulating a both-device stuck-on fault failed. Fault cases above 10 A, where hardware injection was impossible, are evaluated in a chain model calibrated on healthy captures. A closed-form rule relating the lowest diagnosable current to the sampling period, sensor sensitivity and noise reproduces the measured 7.5 A limit and indicates how the test transfers to other hardware.

Authors

Institutions

Publication Details

Journal
Electronics
Published
2026-11-12
DOI
https://doi.org/10.3390/electronics15225256
Primary Topic
Electrical Fault Detection and Protection
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
article

Design and Experimental Validation of an In-Service Self-Test for IGBT Turn-Off Capability in a 400 Hz Current-Limiting Device

Sung‐Chan Park, Jin‐Hyun Park, Hee‐Mun Park
Electronics
Electrical Fault Detection and Protection
article

Design and Experimental Validation of an In-Service Self-Test for IGBT Turn-Off Capability in a 400 Hz Current-Limiting Device

Sung‐Chan Park, Jin‐Hyun Park, Hee‐Mun Park
article en

Abstract

A current-limiting device (CLD) on a 400 Hz shipboard bus protects its load by turning an IGBT path off and diverting the current into a reactor. An IGBT that has failed stuck-on keeps supplying the load and appears healthy, so the loss of turn-off capability can be found only by testing the path in service, without creating a fault current and with the single Hall sensor already installed. This paper designs and validates such a self-test. Short high-impedance pulses at 45° and 225° force a current-path transfer in each of the two anti-series IGBTs, whose transient current drop ratio is the decision metric; a three-of-four criterion and a current-dependent deferral rule confine verdicts to currents the measurement chain can resolve. On production units, no healthy resistive-load capture failed at or above 7.5 A (0 of 25), and all three captures with a jumper emulating a both-device stuck-on fault failed. Fault cases above 10 A, where hardware injection was impossible, are evaluated in a chain model calibrated on healthy captures. A closed-form rule relating the lowest diagnosable current to the sampling period, sensor sensitivity and noise reproduces the measured 7.5 A limit and indicates how the test transfers to other hardware.

ElectronicsVol. 15(22)
Tech University of Korea (KR), Gyeongsang National University (KR)
Industry, innovation and infrastructure
Electrical Fault Detection and Protection
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Laika access coming soon