A Resistive Superconducting Fault-Current Limiter for a Distribution Feeder: Tape Length, Limited Current and Recovery Time

This paper presents a computed design for a fault-current limiter intended for superconducting power devices, with its performance, resource budgets and margins derived from stated assumptions rather than asserted. The headline results are: tape length per phase required at the allowable quench field of 225 m; limited fault current, peak of 2.18 kA; prospective fault current, peak, for comparison of 28.3 kA; ratio of prospective to limited peak current of 13 dimensionless; energy absorbed in the tape during a 100 ms fault after shunt sharing of 196 kJ. Each figure was produced by the deposited computation from the inputs listed in the Methods, and the sensitivity of the conclusions to those inputs is examined in the Discussion. The design is a paper study: it is labelled, on its face and in this abstract, SIMULATED, NOT MEASURED, and no quantity reported here is a measurement of built hardware.

Authors

Publication Details

Journal
Zenodo (CERN European Organization for Nuclear Research)
Published
2026-11-12
DOI
https://doi.org/10.5281/zenodo.24147777
Citations
1
Primary Topic
Superconducting Materials and Applications
Type
article
Field-Weighted Citation Impact
1.32
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
article

A Resistive Superconducting Fault-Current Limiter for a Distribution Feeder: Tape Length, Limited Current and Recovery Time

William Alexander Aldred
1 citations
Zenodo (CERN European Organization for Nuclear Research)
Superconducting Materials and Applications
1.32
article

A Resistive Superconducting Fault-Current Limiter for a Distribution Feeder: Tape Length, Limited Current and Recovery Time

William Alexander Aldred
article en
1 citations

Abstract

This paper presents a computed design for a fault-current limiter intended for superconducting power devices, with its performance, resource budgets and margins derived from stated assumptions rather than asserted. The headline results are: tape length per phase required at the allowable quench field of 225 m; limited fault current, peak of 2.18 kA; prospective fault current, peak, for comparison of 28.3 kA; ratio of prospective to limited peak current of 13 dimensionless; energy absorbed in the tape during a 100 ms fault after shunt sharing of 196 kJ. Each figure was produced by the deposited computation from the inputs listed in the Methods, and the sensitivity of the conclusions to those inputs is examined in the Discussion. The design is a paper study: it is labelled, on its face and in this abstract, SIMULATED, NOT MEASURED, and no quantity reported here is a measurement of built hardware.

Zenodo (CERN European Organization for Nuclear Research)
Openalex Percentile: Top 26%
Superconducting Materials and Applications
1.32
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Laika access coming soon