Effect of flow rate on the performance and fouling of a spiral plate heat exchanger in the phosphoric acid cooling process

The E-2502B cooler in the phosphoric acid concentration unit is used to reduce the temperature of H3PO4 product after concentration before storage. Fluctuations in mass flow rate and outlet temperature indicate the need to evaluate equipment performance to maintain safe and optimal cooling. This study evaluates the performance of the E-2502B Spiral Plate Heat Exchanger (SPHE) based on heat transfer, Log Mean Temperature Difference (LMTD), clean overall coefficient (Uc), design overall coefficient (Ud), fouling factor (Rd), and efficiency. The analysis used actual operating data from 18-27 July 2025, including inlet-outlet temperatures and mass flow rates on the hot and cold sides. The analysis was conducted under the lowest data conditions through heat balance, overall heat-transfer coefficient calculations, and comparison between the actual fouling factor and theoretical limits. The results show an actual cooler efficiency of 50%, with Uc of 853.319 kJ/m²h°C, Ud of 422.689 kJ/m².h.°C, and Rd of 0.001194 m².h.°C/kJ. The actual Rd value exceeds the theoretical range of 0.00018-0.00072 m².h.°C/kJ, indicating fouling that reduces heat-transfer performance. Stable mass flow, periodic cleaning of the acid and cooling-water plates, and flow-rate sensor verification are required to maintain cooler performance.

Authors

Publication Details

Journal
TEKNOSAINS Jurnal Sains Teknologi dan Informatika
Published
2026-11-12
DOI
https://doi.org/10.37373/tekno.v14i1.2523
Primary Topic
Heat Transfer and Optimization
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
article

Effect of flow rate on the performance and fouling of a spiral plate heat exchanger in the phosphoric acid cooling process

Azafilmi Hakiim, Naomi Jeris Simanjuntak, Izran Febrian, Kaori Amelia Putri
TEKNOSAINS Jurnal Sains Teknologi dan Informatika
Heat Transfer and Optimization
article

Effect of flow rate on the performance and fouling of a spiral plate heat exchanger in the phosphoric acid cooling process

Azafilmi Hakiim, Naomi Jeris Simanjuntak, Izran Febrian, Kaori Amelia Putri
article en

Abstract

The E-2502B cooler in the phosphoric acid concentration unit is used to reduce the temperature of H3PO4 product after concentration before storage. Fluctuations in mass flow rate and outlet temperature indicate the need to evaluate equipment performance to maintain safe and optimal cooling. This study evaluates the performance of the E-2502B Spiral Plate Heat Exchanger (SPHE) based on heat transfer, Log Mean Temperature Difference (LMTD), clean overall coefficient (Uc), design overall coefficient (Ud), fouling factor (Rd), and efficiency. The analysis used actual operating data from 18-27 July 2025, including inlet-outlet temperatures and mass flow rates on the hot and cold sides. The analysis was conducted under the lowest data conditions through heat balance, overall heat-transfer coefficient calculations, and comparison between the actual fouling factor and theoretical limits. The results show an actual cooler efficiency of 50%, with Uc of 853.319 kJ/m²h°C, Ud of 422.689 kJ/m².h.°C, and Rd of 0.001194 m².h.°C/kJ. The actual Rd value exceeds the theoretical range of 0.00018-0.00072 m².h.°C/kJ, indicating fouling that reduces heat-transfer performance. Stable mass flow, periodic cleaning of the acid and cooling-water plates, and flow-rate sensor verification are required to maintain cooler performance.

TEKNOSAINS Jurnal Sains Teknologi dan InformatikaVol. 14(1)
Heat Transfer and Optimization
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Laika access coming soon