Sizing a Neighbourhood Cold and Warm Refuge: A Design Rule per 1,000 Residents for Floor Area, Thermal Load and 72-Hour Backup Energy

A sizing model for heated and cooled public refuges, stated per 1,000 residents, derived from population, vulnerable fraction, uptake, overnight occupancy density, envelope and ventilation heat transfer, internal gains and event duration. Base case (vulnerable fraction 0.25, uptake 0.80): 200 occupants plus 16 staff require 4.68 m2 gross per person present, 1,010.0 m2 in total. For a 72-hour heatwave blackout at 40 C in a good building, peak cooling is 51.87 kW thermal, peak electric load 22.48 kW, and the backup-energy bound with reserve is 1,720 kWh or 491 litres of generator diesel, at $1,748.91 capital cost per protected resident; in a poor building cooling rises to 75.99 kW. For a 72-hour winter outage at -15 C, peak heating is 7.44 kW in a good building and 43.70 kW in a poor one. No single typical public building meets the area rule: a 600 m2 school gymnasium covers 59.4% of the required area. SIMULATED, NOT MEASURED.

Authors

Publication Details

Journal
Zenodo (CERN European Organization for Nuclear Research)
Published
2026-11-10
DOI
https://doi.org/10.5281/zenodo.24109982
Primary Topic
Building Energy and Comfort Optimization
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
article

Sizing a Neighbourhood Cold and Warm Refuge: A Design Rule per 1,000 Residents for Floor Area, Thermal Load and 72-Hour Backup Energy

William Alexander Aldred
Zenodo (CERN European Organization for Nuclear Research)
Building Energy and Comfort Optimization
article

Sizing a Neighbourhood Cold and Warm Refuge: A Design Rule per 1,000 Residents for Floor Area, Thermal Load and 72-Hour Backup Energy

William Alexander Aldred
article en

Abstract

A sizing model for heated and cooled public refuges, stated per 1,000 residents, derived from population, vulnerable fraction, uptake, overnight occupancy density, envelope and ventilation heat transfer, internal gains and event duration. Base case (vulnerable fraction 0.25, uptake 0.80): 200 occupants plus 16 staff require 4.68 m2 gross per person present, 1,010.0 m2 in total. For a 72-hour heatwave blackout at 40 C in a good building, peak cooling is 51.87 kW thermal, peak electric load 22.48 kW, and the backup-energy bound with reserve is 1,720 kWh or 491 litres of generator diesel, at $1,748.91 capital cost per protected resident; in a poor building cooling rises to 75.99 kW. For a 72-hour winter outage at -15 C, peak heating is 7.44 kW in a good building and 43.70 kW in a poor one. No single typical public building meets the area rule: a 600 m2 school gymnasium covers 59.4% of the required area. SIMULATED, NOT MEASURED.

Zenodo (CERN European Organization for Nuclear Research)
Building Energy and Comfort Optimization
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Laika access coming soon