The inverse-time characteristic of each relay is a degree of freedom in the coordination of directional overcurrent relays (DOCRs) that most studies leave fixed at standard inverse, optimising only the time multiplier setting (TMS) and plug setting (PS). This paper examined how the IEC 60255-151 characteristic assignment affected the sum of primary operating times on one static DG-integrated benchmark, the 33 kV section of the IEEE 30-bus network with 38 DOCRs and 62 primary/backup pairs. Six assignment rules, including a deterministic rule that selects each relay’s characteristic from its plug-setting multiplier (PSM), were compared under a common optimisation framework, in which a fractional-order, entropy-guided particle swarm–gravitational search from the authors’ earlier work explored the plug settings and a monotone relaxation solved the TMS linear programming problem. All the rules achieved zero coordination violations, and two separate findings emerged. First, characteristic-family selection had a large effect: the objective fell from 29.42 s with uniform standard-inverse settings to 9.16 s with uniform extremely inverse (EI) settings, a reduction of 68.9%. Second, the PSM-driven rule gave a smaller additional improvement, reaching 8.94 s, about 2.4% below uniform EI and the lowest value among the six rules. The relaxation agreed with a general linear programming solver on all the tested candidates, and in a preliminary quantisation check the PSM-driven rule kept a 1.5–2.0% advantage over uniform EI at the same plug settings. The findings were limited to this objective, dataset and static network configuration; implementation on protection hardware was not assessed.

Authors

Institutions

Publication Details

Journal
Energies
Published
2026-11-10
DOI
https://doi.org/10.3390/en19225402
Primary Topic
Power Systems Fault Detection
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
article

DOCR Coordination in DG-Integrated Networks: Characteristic-Curve Selection Using a Hybrid Fractional-Entropy Metaheuristic–LP

Solmaz Kahourzade, Laiq Khan, Mubashar Javed, Amin Mahmoudi
Energies
Power Systems Fault Detection
article

DOCR Coordination in DG-Integrated Networks: Characteristic-Curve Selection Using a Hybrid Fractional-Entropy Metaheuristic–LP

Solmaz Kahourzade, Laiq Khan, Mubashar Javed, Amin Mahmoudi
article en

Abstract

The inverse-time characteristic of each relay is a degree of freedom in the coordination of directional overcurrent relays (DOCRs) that most studies leave fixed at standard inverse, optimising only the time multiplier setting (TMS) and plug setting (PS). This paper examined how the IEC 60255-151 characteristic assignment affected the sum of primary operating times on one static DG-integrated benchmark, the 33 kV section of the IEEE 30-bus network with 38 DOCRs and 62 primary/backup pairs. Six assignment rules, including a deterministic rule that selects each relay’s characteristic from its plug-setting multiplier (PSM), were compared under a common optimisation framework, in which a fractional-order, entropy-guided particle swarm–gravitational search from the authors’ earlier work explored the plug settings and a monotone relaxation solved the TMS linear programming problem. All the rules achieved zero coordination violations, and two separate findings emerged. First, characteristic-family selection had a large effect: the objective fell from 29.42 s with uniform standard-inverse settings to 9.16 s with uniform extremely inverse (EI) settings, a reduction of 68.9%. Second, the PSM-driven rule gave a smaller additional improvement, reaching 8.94 s, about 2.4% below uniform EI and the lowest value among the six rules. The relaxation agreed with a general linear programming solver on all the tested candidates, and in a preliminary quantisation check the PSM-driven rule kept a 1.5–2.0% advantage over uniform EI at the same plug settings. The findings were limited to this objective, dataset and static network configuration; implementation on protection hardware was not assessed.

EnergiesVol. 19(22)
COMSATS University Islamabad (PK), Flinders University (AU), Adelaide University (AU), Monash University (AU), The University of Adelaide (AU)
Power Systems Fault Detection
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Laika access coming soon