Drying a Store Room Below the Silverfish Threshold: Dehumidifier Capacity From a Moisture Balance

Silverfish breed freely in humid rooms and largely stop below about 60 percent relative humidity, so drying a room is a control measure in itself. This study sizes the dehumidifier for a 48 m3 basement store room at 20 C by moisture balance: infiltration of 0.7 air changes per hour of air at 26 C and 80 percent relative humidity, plus 180 g per day of wall and ground ingress. Holding 75 percent relative humidity requires removing 3.99 L per day; holding 60 percent requires 6.08 L per day, which at a stated derating factor of 0.55 for cool-room duty means buying a machine rated at 11.06 L per day. Holding 55 percent needs a 12.33 L per day rating. The originated rule is therefore to select a dehumidifier with a nameplate rating of at least 12 L per day for a room of this size and climate load, and to expect a smaller 'bedroom' unit rated near 7 L per day to stall around the 75 percent level where silverfish continue to breed. This study is simulated, not measured. SIMULATED, NOT MEASURED.

Authors

Publication Details

Journal
Zenodo (CERN European Organization for Nuclear Research)
Published
2026-11-11
DOI
https://doi.org/10.5281/zenodo.24121664
Primary Topic
Building Energy and Comfort Optimization
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
article

Drying a Store Room Below the Silverfish Threshold: Dehumidifier Capacity From a Moisture Balance

William Aldred
Zenodo (CERN European Organization for Nuclear Research)
Building Energy and Comfort Optimization
article

Drying a Store Room Below the Silverfish Threshold: Dehumidifier Capacity From a Moisture Balance

William Aldred
article en

Abstract

Silverfish breed freely in humid rooms and largely stop below about 60 percent relative humidity, so drying a room is a control measure in itself. This study sizes the dehumidifier for a 48 m3 basement store room at 20 C by moisture balance: infiltration of 0.7 air changes per hour of air at 26 C and 80 percent relative humidity, plus 180 g per day of wall and ground ingress. Holding 75 percent relative humidity requires removing 3.99 L per day; holding 60 percent requires 6.08 L per day, which at a stated derating factor of 0.55 for cool-room duty means buying a machine rated at 11.06 L per day. Holding 55 percent needs a 12.33 L per day rating. The originated rule is therefore to select a dehumidifier with a nameplate rating of at least 12 L per day for a room of this size and climate load, and to expect a smaller 'bedroom' unit rated near 7 L per day to stall around the 75 percent level where silverfish continue to breed. This study is simulated, not measured. SIMULATED, NOT MEASURED.

Zenodo (CERN European Organization for Nuclear Research)
Building Energy and Comfort Optimization
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Laika access coming soon