A Porous Ceramic Evaporator Wall for a Single Room in Arid Housing: Computed Indoor Temperature Reduction, Water Use per Degree, and the Humidity Ceiling

SIMULATED, NOT MEASURED. A direct evaporative cooling assembly for arid-climate housing is specified: a porous ceramic/clay evaporator wall of 8.0 m2 net area, gravity-fed, delivering 600 m3/h of air at an evaporative effectiveness of 0.85 into a room of 4.0 x 3.5 x 2.7 m with 28 W/K envelope conductance and 400 W fixed gains. At 40 C and 20 percent relative humidity outside, the simulated indoor temperature is 29.00 C, a reduction of 11.00 C, for 47.21 litres of evaporated water per 12-hour day, i.e. 4.29 litres per day per degree. Across eighteen cases (35, 40 and 45 C; 10-60 percent relative humidity) the water price per degree lies between 4.05 and 5.95 litres per day per degree, and the largest reduction is 15.63 C at 45 C and 10 percent humidity. The humidity ceiling, defined as the humidity at which the reduction first falls below 3.0 C, is 62.7 percent at 40 C (60.3 percent at 35 C, 64.6 percent at 45 C). All numbers are outputs of the deposited computation script; no hardware was built or tested.

Authors

Publication Details

Journal
Zenodo (CERN European Organization for Nuclear Research)
Published
2026-11-10
DOI
https://doi.org/10.5281/zenodo.24108879
Primary Topic
Adsorption and Cooling Systems
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
article

A Porous Ceramic Evaporator Wall for a Single Room in Arid Housing: Computed Indoor Temperature Reduction, Water Use per Degree, and the Humidity Ceiling

William Alexander Aldred
Zenodo (CERN European Organization for Nuclear Research)
Adsorption and Cooling Systems
article

A Porous Ceramic Evaporator Wall for a Single Room in Arid Housing: Computed Indoor Temperature Reduction, Water Use per Degree, and the Humidity Ceiling

William Alexander Aldred
article en

Abstract

SIMULATED, NOT MEASURED. A direct evaporative cooling assembly for arid-climate housing is specified: a porous ceramic/clay evaporator wall of 8.0 m2 net area, gravity-fed, delivering 600 m3/h of air at an evaporative effectiveness of 0.85 into a room of 4.0 x 3.5 x 2.7 m with 28 W/K envelope conductance and 400 W fixed gains. At 40 C and 20 percent relative humidity outside, the simulated indoor temperature is 29.00 C, a reduction of 11.00 C, for 47.21 litres of evaporated water per 12-hour day, i.e. 4.29 litres per day per degree. Across eighteen cases (35, 40 and 45 C; 10-60 percent relative humidity) the water price per degree lies between 4.05 and 5.95 litres per day per degree, and the largest reduction is 15.63 C at 45 C and 10 percent humidity. The humidity ceiling, defined as the humidity at which the reduction first falls below 3.0 C, is 62.7 percent at 40 C (60.3 percent at 35 C, 64.6 percent at 45 C). All numbers are outputs of the deposited computation script; no hardware was built or tested.

Zenodo (CERN European Organization for Nuclear Research)
Adsorption and Cooling Systems
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Laika access coming soon