Safe LPG Storage Geometry for Dense Housing: Hazard Radii, Minimum Separation, and a Communal Vented Store Design

Household LPG cylinders stored on balconies, in alleys and in dense courtyards place neighbouring dwellings inside their hazard radii. From stated simplified models for a jet fire, a flash fire and a vessel burst with fireball, for 5 kg, 15 kg and 45 kg propane cylinders, the governing separations are 7.17 m, 12.52 m and 21.52 m (design values 8 m, 13 m and 22 m), governed in every case by the fireball thermal-dose distance. Jet-fire radii are 3.45 m at 4 kW/m2 for all sizes; flash-fire radii are 3.93 m, 5.66 m and 8.16 m. A small-leak venting requirement of 0.71 m2 free vent area (0.53 m2 low level) is derived. Where available separation is 4.0 m, 2.0 m or 1.5 m no practical individual separation exists even for 5 kg, and the design must change to a communal vented store: 20 households, 5 fire cells of at most 4 x 15 kg cylinders, 12.0 m by 1.8 m by 2.1 m, placed at least 13 m from dwellings, costing 4854.08 USD total or 242.70 USD per household protected, versus 145.0 USD for an individual cage where separation can be met. SIMULATED, NOT MEASURED.

Authors

Publication Details

Journal
Zenodo (CERN European Organization for Nuclear Research)
Published
2026-11-10
DOI
https://doi.org/10.5281/zenodo.24109799
Primary Topic
Fire dynamics and safety research
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
article

Safe LPG Storage Geometry for Dense Housing: Hazard Radii, Minimum Separation, and a Communal Vented Store Design

William Alexander Aldred
Zenodo (CERN European Organization for Nuclear Research)
Fire dynamics and safety research
article

Safe LPG Storage Geometry for Dense Housing: Hazard Radii, Minimum Separation, and a Communal Vented Store Design

William Alexander Aldred
article en

Abstract

Household LPG cylinders stored on balconies, in alleys and in dense courtyards place neighbouring dwellings inside their hazard radii. From stated simplified models for a jet fire, a flash fire and a vessel burst with fireball, for 5 kg, 15 kg and 45 kg propane cylinders, the governing separations are 7.17 m, 12.52 m and 21.52 m (design values 8 m, 13 m and 22 m), governed in every case by the fireball thermal-dose distance. Jet-fire radii are 3.45 m at 4 kW/m2 for all sizes; flash-fire radii are 3.93 m, 5.66 m and 8.16 m. A small-leak venting requirement of 0.71 m2 free vent area (0.53 m2 low level) is derived. Where available separation is 4.0 m, 2.0 m or 1.5 m no practical individual separation exists even for 5 kg, and the design must change to a communal vented store: 20 households, 5 fire cells of at most 4 x 15 kg cylinders, 12.0 m by 1.8 m by 2.1 m, placed at least 13 m from dwellings, costing 4854.08 USD total or 242.70 USD per household protected, versus 145.0 USD for an individual cage where separation can be met. SIMULATED, NOT MEASURED.

Zenodo (CERN European Organization for Nuclear Research)
Fire dynamics and safety research
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Laika access coming soon