Simulation Study on Energy Consumption of the Air Conditioning System of an Office Building in Chongqing Based on DEST

This paper takes an office building in Chongqing as the research object, conducts hourly simulation of annual building energy consumption based on DEST software, and systematically explores the influence patterns of window-to-wall ratio, number of cooling coil rows, fresh air mode, and north-south zoning control on air-conditioning system energy consumption using the controlled variable method. The study shows that reducing the window-to-wall ratio from 0.5 to 0.4 can reduce the average summer cooling load by 25.19%. Through comparison and selection, it is determined that 4 rows of cooling coils combined with variable fresh air, bypass, and north-south zoning strategies can achieve optimal annual cooling and heating energy consumption while meeting air handling requirements.

Authors

Publication Details

Journal
International Journal of Natural Resources and Environmental Studies
Published
2026-11-09
DOI
https://doi.org/10.62051/ijnres.v8n9.06
Primary Topic
Building Energy and Comfort Optimization
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
article

Simulation Study on Energy Consumption of the Air Conditioning System of an Office Building in Chongqing Based on DEST

Yiheng Zhu
International Journal of Natural Resources and Environmental Studies
Building Energy and Comfort Optimization
article

Simulation Study on Energy Consumption of the Air Conditioning System of an Office Building in Chongqing Based on DEST

Yiheng Zhu
article en

Abstract

This paper takes an office building in Chongqing as the research object, conducts hourly simulation of annual building energy consumption based on DEST software, and systematically explores the influence patterns of window-to-wall ratio, number of cooling coil rows, fresh air mode, and north-south zoning control on air-conditioning system energy consumption using the controlled variable method. The study shows that reducing the window-to-wall ratio from 0.5 to 0.4 can reduce the average summer cooling load by 25.19%. Through comparison and selection, it is determined that 4 rows of cooling coils combined with variable fresh air, bypass, and north-south zoning strategies can achieve optimal annual cooling and heating energy consumption while meeting air handling requirements.

International Journal of Natural Resources and Environmental StudiesVol. 8(9)
Building Energy and Comfort Optimization
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Laika access coming soon